Electric Services, major discharger, Island Park, New York. NPDES permit NY0005908 expired Dec 1, 2009; its limits still apply. Last 12 months: over a limit once (last December 2025). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | Iron, total [as Fe], daily maximum | 1.13 mg/L | ≤ 1 mg/L | 13% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Flow rate | daily maximum | report only (gal/d) | all year | 002 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | maximum | ≤ 9 SU | all year | 002 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 002 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 002 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 002 |
| Flow rate | daily maximum | report only (gal/d) | all year | 003 |
| pH | minimum | ≥ 6 SU | all year | 003 |
| pH | maximum | ≤ 9 SU | all year | 003 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 003 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 003 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 003 |
| Flow rate | daily maximum | report only (gal/d) | all year | 004 |
| pH | minimum | ≥ 6 SU | all year | 004 |
| pH | maximum | ≤ 9 SU | all year | 004 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 004 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 004 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 004 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 110 deg F | all year | 005 |
| Thermal Discharge | daily maximum | ≤ 2440 MBTU/hr | all year | 005 |
| Flow rate | monthly average | report only (gal/d) | all year | 005 |
| Flow rate | daily average | report only (gal/d) | all year | 005 |
| Flow rate | daily maximum | report only (gal/d) | all year | 005 |
| Flow rate | daily maximum | report only (gal/d) | all year | 005 |
| Flow rate | daily maximum | report only (gal/d) | all year | 005 |
| Flow rate | daily maximum | report only (gal/d) | all year | 005 |
| pH | minimum | ≥ 6 SU | all year | 005 |
| pH | minimum | ≥ 6 SU | all year | 005 |
| pH | minimum | ≥ 6 SU | all year | 005 |
| pH | minimum | ≥ 6 SU | all year | 005 |
| pH | maximum | ≤ 9 SU | all year | 005 |
| pH | maximum | ≤ 9 SU | all year | 005 |
| pH | maximum | ≤ 9 SU | all year | 005 |
| pH | maximum | ≤ 9 SU | all year | 005 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 005 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 005 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 005 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 005 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 005 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 005 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 005 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 005 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 005 |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 2 mg/L | all year | 005 |
| Chromium, total [as Cr] | daily maximum | ≤ 1 mg/L | all year | 005 |
| Chromium, total [as Cr] | daily maximum | ≤ .5 mg/L | all year | 005 |
| Copper, total [as Cu] | daily maximum | ≤ 1 mg/L | all year | 005 |
| Copper, total [as Cu] | daily maximum | ≤ .5 mg/L | all year | 005 |
| Iron, total [as Fe] | daily maximum | ≤ 1 mg/L | all year | 005 |
| Nickel, total [as Ni] | daily maximum | ≤ 2 mg/L | all year | 005 |
| Zinc, total [as Zn] | daily maximum | ≤ 1 mg/L | all year | 005 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 005 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 005 |
| Chlorine, total residual | daily maximum | ≤ .1 mg/L | all year | 005 |
| Chlorine, total residual | daily maximum | ≤ .2 mg/L | all year | 005 |
| Temp. diff. between intake and discharge | daily maximum | ≤ 30 deg F | all year | 005 |
| Flow rate | daily maximum | report only (gal/d) | all year | 006 |
| pH | minimum | ≥ 6 SU | all year | 006 |
| pH | maximum | ≤ 9 SU | all year | 006 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 006 |
| Oil and grease, hexane extr method | daily maximum | ≤ 15 mg/L | all year | 006 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 006 |
| Flow rate | monthly average | report only (gal/d) | all year | 055 |
| Flow rate | daily average | report only (gal/d) | all year | 055 |
| Flow rate | monthly average | report only (gal/d) | all year | 055 |
| Flow rate | daily maximum | report only (gal/d) | all year | 055 |
| Flow rate | daily maximum | report only (gal/d) | all year | 055 |
| Flow rate | daily maximum | report only (gal/d) | all year | 055 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 055 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 055 |
| Toluene | daily maximum | ≤ 5 ug/L | all year | 055 |
| Toluene | daily maximum | ≤ 5 ug/L | all year | 055 |
| Benzene | daily maximum | ≤ .8 ug/L | all year | 055 |
| Benzene | daily maximum | ≤ .8 ug/L | all year | 055 |
| Ethylbenzene | daily maximum | ≤ 5 ug/L | all year | 055 |
| Ethylbenzene | daily maximum | ≤ 5 ug/L | all year | 055 |
| Naphthalene | daily maximum | ≤ 10 ug/L | all year | 055 |
| Naphthalene | daily maximum | ≤ 10 ug/L | all year | 055 |
| ortho-xylene | daily maximum | ≤ 5 ug/L | all year | 055 |
| ortho-xylene | daily maximum | ≤ 5 ug/L | all year | 055 |
| Xylene, meta & para in combination | daily maximum | ≤ 10 ug/L | all year | 055 |
| Xylene, meta & para in combination | daily maximum | ≤ 10 ug/L | all year | 055 |
| Flow rate | daily average | report only (gal/d) | all year | 056 |
| Flow rate | daily maximum | report only (gal/d) | all year | 056 |
| Oil & Grease | daily average | ≤ 15 mg/L | all year | 056 |
| Toluene | daily average | ≤ 5 ug/L | all year | 056 |
| Benzene | daily average | ≤ .7 ug/L | all year | 056 |
| Benzene | daily maximum | ≤ .8 ug/L | all year | 056 |
| Ethylbenzene | daily average | ≤ 5 ug/L | all year | 056 |
| ortho-xylene | daily average | ≤ 5 ug/L | all year | 056 |
| Xylene, meta & para in combination | daily average | ≤ 10 ug/L | all year | 056 |
| pH | minimum | report only (SU) | all year | GWM |
| pH | maximum | report only (SU) | all year | GWM |
| Chromium, hexavalent [as Cr] | annual maximum | report only (mg/L) | all year | GWM |
| Copper, total [as Cu] | annual maximum | report only (mg/L) | all year | GWM |
| Iron, total [as Fe] | annual maximum | report only (mg/L) | all year | GWM |
| Lead, total [as Pb] | annual maximum | report only (mg/L) | all year | GWM |
| Manganese, total [as Mn] | annual maximum | report only (mg/L) | all year | GWM |
| Nickel, total recoverable | annual maximum | report only (mg/L) | all year | GWM |
| Vanadium, total [as V] | annual maximum | report only (mg/L) | all year | GWM |
| Zinc, total [as Zn] | annual maximum | report only (mg/L) | all year | GWM |
Cited limits by parameter: New York's rules and the federal ones.