Passage Data · Check a report · Use it from your AI

City of Raleigh

Water Supply, Raleigh, North Carolina. NPDES permit NC0082376, in force until May 31, 2029. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 31 days after each period: outfall 001 form M monthly (15 values), outfall 002 form M monthly (14 values), outfall 003 form M monthly (10 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 36 reports late

Limits in force (39)

ParameterStatisticLimitMonthsOutfall
Turbiditydaily maximumreport only (NTU)all year001
pHdaily minimum≥ 6 SUall year001
pHdaily maximum≤ 9 SUall year001
Solids, total suspended30-day average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 45 mg/Lall year001
Nitrogen, total [as N]daily maximumreport only (mg/L)all year001
Nitrogen, total [as N]daily maximumreport only (lb/mo)all year001
Nitrogen, ammonia total [as N]daily maximumreport only (mg/L)all year001
Nitrogen, Kjeldahl, total [as N]daily maximumreport only (mg/L)all year001
Nitrite + Nitrate total [as N]daily maximumreport only (mg/L)all year001
Phosphorus, total [as P]90-day average≤ 2 mg/Lall year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Chlorine, total residualdaily maximum≤ 17 ug/Lall year001
Duration of dischargedaily maximumreport only (hr)all year001
Flow, totaldaily maximumreport only (Mgal/mo)all year001
Turbiditydaily maximumreport only (NTU)all year002
pHdaily minimum≥ 6 SUall year002
pHdaily maximum≤ 9 SUall year002
Solids, total suspended30-day average≤ 30 mg/Lall year002
Solids, total suspendeddaily maximum≤ 45 mg/Lall year002
Nitrogen, total [as N]daily maximumreport only (mg/L)all year002
Nitrogen, total [as N]daily maximumreport only (lb/mo)all year002
Nitrogen, ammonia total [as N]daily maximumreport only (mg/L)all year002
Nitrogen, Kjeldahl, total [as N]daily maximumreport only (mg/L)all year002
Nitrite + Nitrate total [as N]daily maximumreport only (mg/L)all year002
Phosphorus, total [as P]90-day average≤ 2 mg/Lall year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chlorine, total residualdaily maximum≤ 17 ug/Lall year002
Flow, totaldaily maximumreport only (Mgal/mo)all year002
Turbiditydaily maximumreport only (NTU)all year003
pHdaily minimum≥ 6 SUall year003
pHdaily maximum≤ 9 SUall year003
Solids, total suspendeddaily maximumreport only (mg/L)all year003
Nitrogen, total [as N]daily maximumreport only (mg/L)all year003
Nitrogen, ammonia total [as N]daily maximumreport only (mg/L)all year003
Phosphorus, total [as P]90-day average≤ 2 mg/Lall year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualdaily maximumreport only (ug/L)all year003
Duration of dischargedaily maximumreport only (hr)all year003

How strict are these limits?

Cited limits by parameter: North Carolina's rules and the federal ones.

Same industry: the 130 Water Supply permits in North Carolina.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/NC0082376 · MCP: https://passage-data.com/mcp