Columbus County Schools/Board of Education

Elementary And Secondary Schools, Riegelwood, North Carolina. NPDES permit NC0043796, in force until Nov 30, 2026. Last 12 months: over a limit once (last July 2026), 12 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 30 days after each period: form M monthly (18 values)
Renewal application due
Jun 3, 2026 · 180 days before expiry; your permit may set another date
Last report on file
July 2026
Oct 2024 – Sep 2025
0 values over a limit, 18 required values missing, 2 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
July 2026Oxygen, dissolved [DO], daily minimum5.25 mg/L≥ 6 mg/L13%

Limits in force (22)

ParameterStatisticLimitMonths
Temperature, water deg. centigradedaily maximumreport only (deg C)all year
Temperature, water deg. centigradedaily maximumreport only (deg C)all year
Temperature, water deg. centigradedaily maximumreport only (deg C)all year
Oxygen, dissolved [DO]daily minimum≥ 6 mg/Lall year
Oxygen, dissolved [DO]daily maximumreport only (mg/L)all year
Oxygen, dissolved [DO]daily maximumreport only (mg/L)all year
BOD, 5-day, 20 deg. C30-day average≤ 10 mg/LJan, Feb, Mar, Nov, Dec
BOD, 5-day, 20 deg. C30-day average≤ 5 mg/LApr–Oct
BOD, 5-day, 20 deg. Cdaily maximum≤ 15 mg/LJan, Feb, Mar, Nov, Dec
BOD, 5-day, 20 deg. Cdaily maximum≤ 7.5 mg/LApr–Oct
pHdaily minimum≥ 6 SUall year
pHdaily maximum≤ 9 SUall year
Solids, total suspended30-day average≤ 30 mg/Lall year
Solids, total suspendeddaily maximum≤ 45 mg/Lall year
Nitrogen, ammonia total [as N]30-day average≤ 4 mg/LJan, Feb, Mar, Nov, Dec
Nitrogen, ammonia total [as N]30-day average≤ 2 mg/LApr–Oct
Nitrogen, ammonia total [as N]daily maximum≤ 20 mg/LJan, Feb, Mar, Nov, Dec
Nitrogen, ammonia total [as N]daily maximum≤ 10 mg/LApr–Oct
Coliform, fecal MF, MFC broth, 44.5 Cmonthly geometric mean≤ 200 #/100mLall year
Coliform, fecal MF, MFC broth, 44.5 Cdaily maximum≤ 400 #/100mLall year
Flow, in conduit or thru treatment plant30-day average≤ .009 MGDall year
Chlorine, total residualdaily maximum≤ 17 ug/Lall year

How strict are these limits?

Cited limits by parameter: North Carolina's rules and the federal ones.

Same industry: the 78 Educational Services permits in North Carolina.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history