Passage Data · Check a report · Use it from your AI

Town of Plymouth

Sewage treatment plant, Plymouth, North Carolina. NPDES permit NC0020028, in force until Aug 31, 2028. Last 12 months: no values over a limit, 3 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form M monthly (13 values)
Renewal application due
Mar 4, 2028 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 25 required values missing, 2 of 12 reports late

Limits in force (17)

ParameterStatisticLimitMonths
Temperature, water deg. centigradedaily maximumreport only (deg C)all year
BOD, 5-day, 20 deg. C7-day average≤ 28.5 mg/LApr–Oct
BOD, 5-day, 20 deg. C7-day average≤ 45 mg/LJan, Feb, Mar, Nov, Dec
BOD, 5-day, 20 deg. C30-day average≤ 19 mg/LApr–Oct
BOD, 5-day, 20 deg. C30-day average≤ 30 mg/LJan, Feb, Mar, Nov, Dec
BOD, 5-day, 20 deg. Cdaily maximumreport only (mg/L)all year
pHdaily minimum≥ 6 SUall year
pHdaily maximum≤ 9 SUall year
Solids, total suspended7-day average≤ 45 mg/Lall year
Solids, total suspended30-day average≤ 30 mg/Lall year
Solids, total suspendeddaily maximumreport only (mg/L)all year
Nitrogen, ammonia total [as N]7-day average≤ 10.5 mg/LApr–Oct
Nitrogen, ammonia total [as N]7-day average≤ 21 mg/LJan, Feb, Mar, Nov, Dec
Nitrogen, ammonia total [as N]30-day average≤ 7 mg/LApr–Oct
Nitrogen, ammonia total [as N]30-day average≤ 14 mg/LJan, Feb, Mar, Nov, Dec
Coliform, fecal MF, MFC broth, 44.5 Cdaily maximumreport only (#/100mL)all year
Flow, in conduit or thru treatment plant30-day average≤ .8 MGDall year

How strict are these limits?

Cited limits by parameter: North Carolina's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/NC0020028 · MCP: https://passage-data.com/mcp