Passage Data · Check a report · Use it from your AI
Electric Services, major discharger, Sallis, Mississippi. NPDES permit MS0056928, in force until Oct 31, 2028. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. fahrenheit | daily maximum | report only (deg F) | all year | 001 |
| Temperature, water deg. fahrenheit | monthly average | report only (deg F) | May–Oct | 001 |
| Temperature, water deg. fahrenheit | daily maximum | report only (deg F) | May–Oct | 001 |
| Temperature, water deg. fahrenheit | monthly average | report only (deg F) | May–Oct | 001 |
| Temperature, water deg. fahrenheit | daily maximum | report only (deg F) | May–Oct | 001 |
| Temp. diff. between samp. & upstrm deg. F | daily maximum | ≤ 5 deg F | May–Oct | 001 |
| Specific conductance | monthly average | report only (umho/cm) | all year | 001 |
| Specific conductance | daily maximum | report only (umho/cm) | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Zinc, total recoverable | monthly average | ≤ 1 mg/L | all year | 001 |
| Zinc, total recoverable | daily maximum | ≤ 1 mg/L | all year | 001 |
| Zinc, total recoverable | monthly average | ≤ 12.18 lb/d | all year | 001 |
| Zinc, total recoverable | daily maximum | ≤ 12.18 lb/d | all year | 001 |
| Chromium, total recoverable | monthly average | ≤ .2 mg/L | all year | 001 |
| Chromium, total recoverable | daily maximum | ≤ .2 mg/L | all year | 001 |
| Chromium, total recoverable | monthly average | ≤ 2.44 lb/d | all year | 001 |
| Chromium, total recoverable | daily maximum | ≤ 2.44 lb/d | all year | 001 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Chlorine, total residual | monthly average | ≤ .1 mg/L | all year | 001 |
| Chlorine, total residual | daily maximum | ≤ .1 mg/L | all year | 001 |
| Chlorine, free available | monthly average | ≤ .035 mg/L | all year | 001 |
| Chlorine, free available | daily maximum | ≤ .035 mg/L | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | monthly maximum | ≤ 9 SU | all year | 002 |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year | 002 |
| Solids, total suspended | monthly maximum | ≤ 100 mg/L | all year | 002 |
| Solids, total suspended | monthly average | ≤ 18 lb/d | all year | 002 |
| Solids, total suspended | monthly maximum | ≤ 60 lb/d | all year | 002 |
| Oil & Grease | monthly average | ≤ 15 mg/L | all year | 002 |
| Oil & Grease | monthly maximum | ≤ 20 mg/L | all year | 002 |
| Oil & Grease | monthly average | ≤ 9 lb/d | all year | 002 |
| Oil & Grease | monthly maximum | ≤ 12 lb/d | all year | 002 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 002 |
| Flow, in conduit or thru treatment plant | monthly maximum | report only (MGD) | all year | 002 |
Cited limits by parameter: Mississippi's rules and the federal ones.
Same industry: the 20 Electric Services permits in Mississippi.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/MS0056928 · MCP: https://passage-data.com/mcp