Passage Data · Check a report · Use it from your AI

Lazy Acres Home Owners Association, Inc.

Sewerage Systems, Bowling Green, Missouri. NPDES permit MO0129984, in force until Jun 30, 2030. Last 12 months: over a limit 4 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 29 days after each period: form Q quarterly (16 values)
Last report on file
June 2026
Oct 2024 – Sep 2025
13 values over a limit, 16 required values missing, 1 of 4 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
December 2025Nitrogen, ammonia total [as N], daily maximum15.13≤ 7.5 mg/L102%
December 2025Nitrogen, ammonia total [as N], monthly average15.13≤ 2.9 mg/L422%
June 2026Nitrogen, ammonia total [as N], daily maximum10.07≤ 3.6 mg/L180%
June 2026Nitrogen, ammonia total [as N], monthly average10.07≤ 1.4 mg/L619%

Limits in force (22)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]daily minimumreport only (mg/L)Apr–Dec
Oxygen, dissolved [DO]monthly average minimumreport only (mg/L)Apr–Dec
BOD, 5-day, 20 deg. Cweekly average≤ 45 mg/Lall year
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/Lall year
pHminimum≥ 6.5 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendedweekly average≤ 45 mg/Lall year
Solids, total suspendedmonthly average≤ 30 mg/Lall year
Nitrogen, ammonia total [as N]daily maximum≤ 7.5 mg/LOct–Dec
Nitrogen, ammonia total [as N]daily maximum≤ 3.6 mg/LJul–Sep
Nitrogen, ammonia total [as N]daily maximum≤ 7.5 mg/LJan–Mar
Nitrogen, ammonia total [as N]daily maximum≤ 3.6 mg/LApr–Jun
Nitrogen, ammonia total [as N]monthly average≤ 2.9 mg/LOct–Dec
Nitrogen, ammonia total [as N]monthly average≤ 1.3 mg/LJul–Sep
Nitrogen, ammonia total [as N]monthly average≤ 2.7 mg/LJan–Mar
Nitrogen, ammonia total [as N]monthly average≤ 1.4 mg/LApr–Jun
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year
Chlorine, total residualdaily maximum≤ 17 ug/LApr–Dec
Chlorine, total residualmonthly average≤ 8 ug/LApr–Dec
E. colidaily maximum≤ 630 #/100mLApr–Dec
E. coli30-day geometric mean≤ 126 #/100mLApr–Dec

How strict are these limits?

Cited limits by parameter: Missouri's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/MO0129984 · MCP: https://passage-data.com/mcp