Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Fulton, Missouri. NPDES permit MO0112224 expired Sep 30, 2024; its limits still apply. Last 12 months: over a limit 12 times (last June 2026), 1 of 3 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | E. coli, 30-day geometric mean | 4760 | ≤ 206 #/100mL | 2211% |
| December 2025 | E. coli, 7-day geometric mean | 4760 | ≤ 1030 #/100mL | 362% |
| December 2025 | Nitrogen, ammonia total [as N], daily maximum | 25.1 | ≤ 6.6 mg/L | 280% |
| December 2025 | Nitrogen, ammonia total [as N], monthly average | 25.1 | ≤ 2.9 mg/L | 766% |
| March 2026 | Nitrogen, ammonia total [as N], daily maximum | 23.3 | ≤ 6.6 mg/L | 253% |
| March 2026 | Nitrogen, ammonia total [as N], monthly average | 23.3 | ≤ 2.9 mg/L | 703% |
| March 2026 | Solids, total suspended, monthly average | 167 | ≤ 80 mg/L | 109% |
| March 2026 | Solids, total suspended, weekly average | 167 | ≤ 120 mg/L | 39% |
| June 2026 | E. coli, 30-day geometric mean | 260000 | ≤ 206 #/100mL | — |
| June 2026 | E. coli, 7-day geometric mean | 260000 | ≤ 1030 #/100mL | 25143% |
| June 2026 | Nitrogen, ammonia total [as N], daily maximum | 6.4 | ≤ 3.6 mg/L | 78% |
| June 2026 | Nitrogen, ammonia total [as N], monthly average | 6.4 | ≤ 1.4 mg/L | 357% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| BOD, 5-day, 20 deg. C | weekly average | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | monthly average | ≤ 45 mg/L | all year |
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | weekly average | ≤ 120 mg/L | all year |
| Solids, total suspended | monthly average | ≤ 80 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 3.6 mg/L | Apr–Sep |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 6.6 mg/L | Jan, Feb, Mar, Oct, Nov, Dec |
| Nitrogen, ammonia total [as N] | monthly average | ≤ 1.4 mg/L | Apr–Sep |
| Nitrogen, ammonia total [as N] | monthly average | ≤ 2.9 mg/L | Jan, Feb, Mar, Oct, Nov, Dec |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| E. coli | 7-day geometric mean | ≤ 1030 #/100mL | Apr–Dec |
| E. coli | 30-day geometric mean | ≤ 206 #/100mL | Apr–Dec |
Cited limits by parameter: Missouri's rules and the federal ones.