Water Supply, Grantsville, Maryland. NPDES permit MD0063274, in force until Feb 28, 2029. Last 12 months: over a limit 20 times (last August 2026), 2 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | pH, minimum | 6.4 SU | ≥ 6.5 SU | — |
| December 2025 | pH, minimum | 6.4 SU | ≥ 6.5 SU | — |
| February 2026 | pH, minimum | 6.31 SU | ≥ 6.5 SU | — |
| April 2026 | Chlorine, total residual, maximum | .26 mg/L | < .1 mg/L | 160% |
| April 2026 | Iron, total [as Fe], quarterly average | 2.29 mg/L | ≤ 2 mg/L | 15% |
| April 2026 | pH, minimum | 6.34 SU | ≥ 6.5 SU | — |
| May 2026 | Chlorine, total residual, maximum | .98 mg/L | < .1 mg/L | 880% |
| May 2026 | Iron, total [as Fe], daily maximum | 3.27 mg/L | ≤ 3 mg/L | 9% |
| May 2026 | Iron, total [as Fe], quarterly average | 3.27 mg/L | ≤ 2 mg/L | 64% |
| May 2026 | pH, minimum | 5.94 SU | ≥ 6.5 SU | — |
| June 2026 | Chlorine, total residual, maximum | .41 mg/L | < .1 mg/L | 310% |
| June 2026 | pH, minimum | 6.4 SU | ≥ 6.5 SU | — |
| July 2026 | Chlorine, total residual, maximum | .15 mg/L | < .1 mg/L | 50% |
| July 2026 | Iron, total [as Fe], daily maximum | 4.75 mg/L | ≤ 3 mg/L | 58% |
| July 2026 | Iron, total [as Fe], quarterly average | 4.75 mg/L | ≤ 2 mg/L | 138% |
| July 2026 | pH, minimum | 6.23 SU | ≥ 6.5 SU | — |
| August 2026 | Chlorine, total residual, maximum | .1 mg/L | < .1 mg/L | 0% |
| August 2026 | Iron, total [as Fe], daily maximum | 3.42 mg/L | ≤ 3 mg/L | 14% |
| August 2026 | Iron, total [as Fe], quarterly average | 3.42 mg/L | ≤ 2 mg/L | 71% |
| August 2026 | pH, minimum | 6.31 SU | ≥ 6.5 SU | — |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Solids, total suspended | quarterly average | ≤ 20 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 30 mg/L | all year |
| Iron, total [as Fe] | quarterly average | ≤ 2 mg/L | all year |
| Iron, total [as Fe] | daily maximum | ≤ 3 mg/L | all year |
| Flow, in conduit or thru treatment plant | average | report only (MGD) | all year |
| Chlorine, total residual | maximum | < .1 mg/L | all year |
| Flow, discharge | monthly average | report only (MGD) | all year |
Cited limits by parameter: Maryland's rules and the federal ones.
Same industry: the 18 Water Supply permits in Maryland.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/MD0063274 · MCP: https://passage-data.com/mcp