Passage Data · Check a report · Use it from your AI
Water Supply, Baltimore, Maryland. NPDES permit MD0003042 expired May 31, 2024; its limits still apply. Last 12 months: over a limit 4 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| February 2026 | Chlorine, total residual, maximum | .136 mg/L | ≤ .1 mg/L | 36% |
| July 2026 | Solids, total suspended, maximum monthly average | 71.5 mg/L | ≤ 20 mg/L | 258% |
| July 2026 | Solids, total suspended, maximum daily average | 272 mg/L | ≤ 30 mg/L | 807% |
| August 2026 | Solids, total suspended, maximum daily average | 37.6 mg/L | ≤ 30 mg/L | 25% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Solids, total suspended | maximum monthly average | ≤ 20 mg/L | all year |
| Solids, total suspended | maximum daily average | ≤ 30 mg/L | all year |
| Aluminum, total recoverable | maximum monthly average | ≤ 1 mg/L | all year |
| Aluminum, total recoverable | maximum daily average | ≤ 2 mg/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | maximum | ≤ .1 mg/L | all year |
Cited limits by parameter: Maryland's rules and the federal ones.
Same industry: the 18 Water Supply permits in Maryland.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/MD0003042 · MCP: https://passage-data.com/mcp