Louisiana Generating LLC

Electric Services, major discharger, New Roads, Louisiana. NPDES permit LA0054135, in force until Aug 31, 2027. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form A monthly (14 values), outfall 001 form DA quarterly (11 values), outfall 001 form PI quarterly (11 values), outfall 001 form Q quarterly (1 value), outfall 003 form A monthly (6 values), outfall 101 form A monthly (8 values), and 5 more forms
Renewal application due
Mar 4, 2027 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 75 reports late

Limits in force (77)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitmonthly average≤ 100 deg Fall year001
Temperature, water deg. fahrenheitdaily maximum≤ 105 deg Fall year001
pHminimumreport only (SU)all year001
pHmaximumreport only (SU)all year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendeddaily maximum≤ 100 mg/Lall year001
Oil & Greasemonthly average≤ 15 mg/Lall year001
Oil & Greasemonthly average≤ 15 mg/Lall year001
Oil & Greasedaily maximum≤ 20 mg/Lall year001
Oil & Greasedaily maximum≤ 20 mg/Lall year001
Carbon, tot organic [TOC]daily maximum≤ 50 mg/Lall year001
Copper, total [as Cu]monthly average≤ 1 mg/Lall year001
Copper, total [as Cu]daily maximum≤ 1 mg/Lall year001
Iron, total [as Fe]monthly average≤ 1 mg/Lall year001
Iron, total [as Fe]daily maximum≤ 1 mg/Lall year001
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #148-hour minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #148-hour minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #248-hour minimumreport only (pass=0;fail=1)all year001
Whole effluent toxicity - retest #248-hour minimumreport only (pass=0;fail=1)all year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Whole Effluent Toxicity - Retest #3monthly average minimumreport only (pass=0;fail=1)all year001
Whole Effluent Toxicity - Retest #3monthly average minimumreport only (pass=0;fail=1)all year001
Whole Effluent Toxicity - Retest #348-hour minimumreport only (pass=0;fail=1)all year001
Whole Effluent Toxicity - Retest #348-hour minimumreport only (pass=0;fail=1)all year001
pH range excursions, > 60 minutesmonthly total≤ 0 occur/moall year001
pH range excursions, monthly total accummonthly total≤ 446 minall year001
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulexmonthly average minimumreport only (pass=0;fail=1)all year001
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex48-hour minimumreport only (pass=0;fail=1)all year001
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all year001
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (pass=0;fail=1)all year001
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulexmonthly average minimumreport only (%)all year001
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulex48-hour minimumreport only (%)all year001
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelasmonthly average minimumreport only (%)all year001
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelas48-hour minimumreport only (%)all year001
Coef Of Var Static Renewal 48Hr Acute D. pulexmaximumreport only (%)all year001
Coef Of Var Static Renewal 48Hr Acute Pimephales promelasmaximumreport only (%)all year001
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year003
Temperature, water deg. fahrenheitdaily maximum≤ 118 deg Fall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualdaily maximum≤ .2 mg/Lall year003
Chlorine, total residualdaily maximum≤ 56.3 lb/dall year003
pHinstantaneous minimum≥ 6 SUall year101
pHinstantaneous maximum≤ 9 SUall year101
Chromium, total [as Cr]monthly average≤ .2 mg/Lall year101
Chromium, total [as Cr]daily maximum≤ .2 mg/Lall year101
Zinc, total [as Zn]monthly average≤ 1 mg/Lall year101
Zinc, total [as Zn]daily maximum≤ 1 mg/Lall year101
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year101
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year101
Chlorine, free availablemonthly average≤ .2 mg/Lall year101
Chlorine, free availabledaily maximum≤ .5 mg/Lall year101
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/Lall year201
BOD, 5-day, 20 deg. Cweekly average≤ 45 mg/Lall year201
Solids, total suspendedmonthly average≤ 30 mg/Lall year201
Solids, total suspendedweekly average≤ 45 mg/Lall year201
Flow, in conduit or thru treatment plantweekly averagereport only (MGD)all year201
Coliform, fecal generalmonthly average≤ 200 #/100mLall year201
Coliform, fecal generaldaily maximum≤ 400 #/100mLall year201
pHinstantaneous minimum≥ 6 SUall year401
pHinstantaneous maximum≤ 9 SUall year401
Solids, total suspendeddaily maximum≤ 90 mg/Lall year401
Solids, total suspendeddaily maximum≤ 90 mg/Lall year401
Oil & Greasedaily maximum≤ 15 mg/Lall year401
Carbon, tot organic [TOC]daily maximum≤ 50 mg/Lall year401
Lead, total [as Pb]daily maximum≤ 50 ug/Lall year401
Benzenedaily maximum≤ 50 ug/Lall year401
BTEXdaily maximum≤ 250 ug/Lall year401
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year401
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year401
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all yearIT01
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all yearIT01

How strict are these limits?

Cited limits by parameter: Louisiana's rules and the federal ones.

Same industry: the 29 Electric Services permits in Louisiana.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/LA0054135 · MCP: https://passage-data.com/mcp