Passage Data · Check a report · Use it from your AI

Duke Energy Kentucky Inc - East Bend Station

Electric Services, major discharger, Union, Kentucky. NPDES permit KY0040444, in force until Sep 30, 2030. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form 1 monthly (10 values), outfall 001 form 1B monthly (4 values), outfall 003 form 1 monthly (4 values), outfall 007 form 1 monthly (5 values), outfall 010 form 1 monthly (7 values), outfall 011 form 1 monthly (5 values), and 4 more forms
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 77 reports late

Limits in force (56)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximum≤ 110 deg Fall year001
pHminimum≥ 6 SUall year001
pHdaily maximum≤ 9 SUall year001
Oil & Greasemonthly average≤ 11.7 mg/Lall year001
Oil & Greasedaily maximum≤ 15.6 mg/Lall year001
Hardness, total [as CaCO3]monthly averagereport only (mg/L)all year001
Hardness, total [as CaCO3]daily maximumreport only (mg/L)all year001
Copper, total recoverablemonthly average≤ .052 mg/Lall year001
Copper, total recoverabledaily maximum≤ .052 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Suspended Solids, Totalmonthly average≤ 30 mg/Lall year001
Suspended Solids, Totaldaily maximum≤ 80.1 mg/Lall year001
Toxicity, Acutedaily maximum≤ 1 tox acuteall year001
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year003
Temperature, water deg. fahrenheitdaily maximum≤ 110 deg Fall year003
pHminimum≥ 6 SUall year003
pHdaily maximum≤ 9 SUall year003
Hardness, total [as CaCO3]monthly averagereport only (mg/L)all year003
Hardness, total [as CaCO3]daily maximumreport only (mg/L)all year003
Iron, total recoverablemonthly averagereport only (mg/L)all year003
Iron, total recoverabledaily maximumreport only (mg/L)all year003
Copper, total recoverablemonthly averagereport only (mg/L)all year003
Copper, total recoverabledaily maximumreport only (mg/L)all year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/Lall year007
BOD, 5-day, 20 deg. Cmaximum weekly average≤ 45 mg/Lall year007
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year007
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year007
Chlorine, total residualminimum≥ .5 mg/Lall year007
Zinc, total recoverablemonthly average≤ 1 mg/Lall year010
Zinc, total recoverabledaily maximum≤ 1 mg/Lall year010
Chromium, total recoverablemonthly average≤ .2 mg/Lall year010
Chromium, total recoverabledaily maximum≤ .2 mg/Lall year010
Oxidants, total residualmonthly averagereport only (mg/L)all year010
Oxidants, total residualdaily maximum≤ .2 mg/Lall year010
Priority Pollutantsmonthly average≤ 0 mg/Lall year010
Priority Pollutantsdaily maximum≤ 0 mg/Lall year010
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year010
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year010
Chlorine, free availablemonthly average≤ .2 mg/Lall year010
Chlorine, free availabledaily maximum≤ .5 mg/Lall year010
Duration of Oxidant Additiondaily maximum≤ 120 min/dall year010
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year011
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year011
Hardness, total [as CaCO3]monthly averagereport only (mg/L)all year011
Hardness, total [as CaCO3]daily maximumreport only (mg/L)all year011
Iron, total recoverablemonthly averagereport only (mg/L)all year011
Iron, total recoverabledaily maximumreport only (mg/L)all year011
Copper, total recoverablemonthly averagereport only (mg/L)all year011
Copper, total recoverabledaily maximumreport only (mg/L)all year011
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year011
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year011
Cooling Water Intake Inspectiondaily maximumreport only (pass=0;fail=1)all year011

How strict are these limits?

Cited limits by parameter: Kentucky's rules and the federal ones.

Same industry: the 29 Electric Services permits in Kentucky.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/KY0040444 · MCP: https://passage-data.com/mcp