Passage Data · Check a report · Use it from your AI

Kentucky Utilities - EW Brown Generating Station

Electric Services, major discharger, Harrodsburg, Kentucky. NPDES permit KY0002020, in force until Jun 30, 2030. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: outfall 001 form 2 quarterly (6 values), outfall 003 form 1 monthly (13 values), outfall 004 form 1 monthly (6 values), outfall 005 form 1 monthly (5 values), outfall 006 form 1 monthly (9 values), outfall 006 form 2 quarterly (4 values), and 4 more forms
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 82 reports late

Limits in force (100)

ParameterStatisticLimitMonthsOutfall
pHminimum≥ 6 SUall year001
pHdaily maximum≤ 9 SUall year001
Solids, total suspendedmonthly averagereport only (mg/L)all year001
Solids, total suspendeddaily maximum≤ 100 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year003
Temperature, water deg. fahrenheitdaily maximum≤ 110 deg Fall year003
pHminimum≥ 6 SUall year003
pHdaily maximum≤ 9 SUall year003
Hardness, total [as CaCO3]monthly averagereport only (mg/L)all year003
Hardness, total [as CaCO3]daily maximumreport only (mg/L)all year003
Chromium, total [as Cr]monthly average≤ .2 mg/Lall year003
Chromium, total [as Cr]daily maximum≤ .2 mg/Lall year003
Zinc, total [as Zn]monthly average≤ .175 mg/Lall year003
Zinc, total [as Zn]daily maximum≤ .175 mg/Lall year003
Oxidants, total residualmonthly averagereport only (mg/L)all year003
Oxidants, total residualdaily maximum≤ .2 mg/Lall year003
Priority Pollutantsmonthly average≤ 0 mg/Lall year003
Priority Pollutantsdaily maximum≤ 0 mg/Lall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualmonthly averagereport only (mg/L)all year003
Chlorine, total residualdaily maximum≤ .019 mg/Lall year003
Chlorine, free availablemonthly average≤ .2 mg/Lall year003
Chlorine, free availabledaily maximum≤ .5 mg/Lall year003
Duration of Oxidant Additiondaily maximum≤ 120 min/dall year003
Iron, total recoverablemonthly average≤ 1 mg/Lall year004
Iron, total recoverabledaily maximum≤ 1 mg/Lall year004
Copper, total recoverablemonthly average≤ 1 mg/Lall year004
Copper, total recoverabledaily maximum≤ 1 mg/Lall year004
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year004
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year004
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year005
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year005
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year005
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year005
Cooling Water Intake Inspectionmaximumreport only (pass=0;fail=1)all year005
pHminimum≥ 6 SUall year006
pHmaximum≤ 9 SUall year006
Solids, total suspendedmonthly average≤ 30 mg/Lall year006
Solids, total suspendedmonthly average≤ 30 mg/Lall year006
Solids, total suspendeddaily maximum≤ 89.4 mg/Lall year006
Solids, total suspendeddaily maximum≤ 91.6 mg/Lall year006
Oil & Greasemonthly average≤ 13.5 mg/Lall year006
Oil & Greasemonthly average≤ 13.8 mg/Lall year006
Oil & Greasedaily maximum≤ 17.7 mg/Lall year006
Oil & Greasedaily maximum≤ 18.7 mg/Lall year006
Selenium, total recoverablemonthly average≤ .127 mg/Lall year006
Selenium, total recoverabledaily maximumreport only (mg/L)all year006
Selenium, dry weightmaximum≤ 8.6 mg/kgall year006
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year006
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year006
Flow, process wastewaterdaily maximum≤ 33339 gal/dall year006
Toxicity, Acutemaximum≤ 1 tox acuteall year006
Hardness, total [as CaCO3]monthly averagereport only (mg/L)all year006A
Hardness, total [as CaCO3]daily maximumreport only (mg/L)all year006A
Arsenic, total recoverablemonthly average≤ 1.03 mg/Lall year006A
Arsenic, total recoverabledaily maximum≤ 1.03 mg/Lall year006A
Iron, total recoverablemonthly average≤ 12.2 mg/Lall year006A
Iron, total recoverabledaily maximum≤ 12.2 mg/Lall year006A
Selenium, total recoverablemonthly averagereport only (mg/L)all year006A
Selenium, total recoverabledaily maximumreport only (mg/L)all year006A
Thallium, total recoverablemonthly average≤ .011 mg/Lall year006A
Thallium, total recoverabledaily maximumreport only (mg/L)all year006A
Beryllium, total recoverable [as Be]monthly average≤ .24 mg/Lall year006A
Beryllium, total recoverable [as Be]daily maximumreport only (mg/L)all year006A
Nickel, total recoverablemonthly average≤ 2.04 mg/Lall year006A
Nickel, total recoverabledaily maximum≤ 3.4 mg/Lall year006A
Silver total recoverablemonthly averagereport only (mg/L)all year006A
Silver total recoverabledaily maximum≤ .049 mg/Lall year006A
Zinc, total recoverablemonthly average≤ .859 mg/Lall year006A
Zinc, total recoverabledaily maximum≤ .859 mg/Lall year006A
Cadmium, total recoverablemonthly average≤ .015 mg/Lall year006A
Cadmium, total recoverabledaily maximum≤ .015 mg/Lall year006A
Lead, total recoverablemonthly average≤ .15 mg/Lall year006A
Lead, total recoverabledaily maximum≤ .916 mg/Lall year006A
Chromium, total recoverablemonthly average≤ 6 mg/Lall year006A
Chromium, total recoverabledaily maximumreport only (mg/L)all year006A
Copper, total recoverablemonthly average≤ .106 mg/Lall year006A
Copper, total recoverabledaily maximum≤ .106 mg/Lall year006A
Antimony, total recoverablemonthly average≤ .336 mg/Lall year006A
Antimony, total recoverabledaily maximumreport only (mg/L)all year006A
Mercury, total recoverablemonthly average≤ .000046 mg/gall year006A
Mercury, total recoverabledaily maximum≤ .0013 mg/gall year006A
Toxicity, Acutemaximumreport only (tox acute)all year006A
pHminimum≥ 6 SUall year008
pHdaily maximum≤ 9 SUall year008
Solids, total suspendedmonthly averagereport only (mg/L)all year008
Solids, total suspendeddaily maximumreport only (mg/L)all year008
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year008
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year008
pHminimum≥ 6 SUall year009
pHdaily maximum≤ 9 SUall year009
Solids, total suspendedmonthly averagereport only (mg/L)all year009
Solids, total suspendeddaily maximumreport only (mg/L)all year009
Oil & Greasemonthly averagereport only (mg/L)all year009
Oil & Greasedaily maximum≤ 15 mg/Lall year009
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year009
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year009

How strict are these limits?

Cited limits by parameter: Kentucky's rules and the federal ones.

Same industry: the 29 Electric Services permits in Kentucky.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/KY0002020 · MCP: https://passage-data.com/mcp