Passage Data · Check a report · Use it from your AI
Electric Services, Keokuk, Iowa. NPDES permit IA0033600, in force until Jul 31, 2027. Last 12 months: over a limit 2 times (last July 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Outfall | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|---|
| November 2025 | 027 | Oil & Grease, 30-day average | 15.8 | ≤ 15 mg/L | 5% |
| July 2026 | 035 | Solids, total suspended, 7-day average | 53 | ≤ 45 mg/L | 18% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| pH | daily minimum | ≥ 6 SU | all year | 012 |
| pH | daily maximum | ≤ 9 SU | all year | 012 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 012 |
| Solids, total suspended | 7-day average | ≤ 45 mg/L | all year | 012 |
| Oil & Grease | 30-day average | ≤ 10 mg/L | all year | 012 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 012 |
| pH | daily minimum | ≥ 6 SU | all year | 027 |
| pH | daily maximum | ≤ 9 SU | all year | 027 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 027 |
| Solids, total suspended | 7-day average | ≤ 45 mg/L | all year | 027 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 027 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 027 |
| pH | daily minimum | ≥ 6 SU | all year | 035 |
| pH | daily maximum | ≤ 9 SU | all year | 035 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 035 |
| Solids, total suspended | 7-day average | ≤ 45 mg/L | all year | 035 |
| Solids, total suspended | 30-day average | ≤ .25 lb/d | all year | 035 |
| Solids, total suspended | 7-day average | ≤ .38 lb/d | all year | 035 |
| E. coli | geometric mean | ≤ 126 #/100mL | Mar–Nov | 035 |
| BOD, carbonaceous [5 day, 20 C] | 30-day average | ≤ 25 mg/L | all year | 035 |
| BOD, carbonaceous [5 day, 20 C] | 7-day average | ≤ 40 mg/L | all year | 035 |
| BOD, carbonaceous [5 day, 20 C] | 30-day average | ≤ .21 lb/d | all year | 035 |
| BOD, carbonaceous [5 day, 20 C] | 7-day average | ≤ .33 lb/d | all year | 035 |
Cited limits by parameter: Iowa's rules and the federal ones.
Same industry: the 14 Electric Services permits in Iowa.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/IA0033600 · MCP: https://passage-data.com/mcp