Passage Data · Check a report · Use it from your AI
Electric Services, Cedar Falls, Iowa. NPDES permit IA0002534, in force until May 31, 2027. Last 12 months: over a limit 2 times (last November 2025), 15 required values missing. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Copper, total [as Cu], 30-day average | .0371 | ≤ .01874 mg/L | 98% |
| November 2025 | Copper, total [as Cu], daily maximum | .1113 | ≤ .02851 mg/L | 290% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. fahrenheit | 30-day average | ≤ 89.6 deg F | Jul | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 84.9 deg F | Oct | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 71.6 deg F | Dec | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 87 deg F | Jun | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 64 deg F | Jan | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 89.6 deg F | Aug | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 82.5 deg F | Apr | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 80.6 deg F | Nov | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 75.9 deg F | Mar | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 64 deg F | Feb | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 87.9 deg F | Sep | 001 |
| Temperature, water deg. fahrenheit | 30-day average | ≤ 82.5 deg F | May | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.6 deg F | Jul | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.8 deg F | Oct | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 90.4 deg F | Dec | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.8 deg F | Jun | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 90.5 deg F | Jan | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.6 deg F | Aug | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.9 deg F | Apr | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 90.2 deg F | Nov | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 90.3 deg F | Mar | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 90.5 deg F | Feb | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.8 deg F | Sep | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 89.9 deg F | May | 001 |
| pH | daily minimum | ≥ 6.5 SU | all year | 001 |
| pH | daily maximum | ≤ 9 SU | all year | 001 |
| Copper, total [as Cu] | 30-day average | ≤ .01874 mg/L | all year | 001 |
| Copper, total [as Cu] | daily maximum | ≤ .02851 mg/L | all year | 001 |
| Copper, total [as Cu] | 30-day average | ≤ 1.324 lb/d | all year | 001 |
| Copper, total [as Cu] | daily maximum | ≤ 2.079 lb/d | all year | 001 |
| Chlorine, total residual | 30-day average | ≤ .012 mg/L | all year | 001 |
| Chlorine, total residual | daily maximum | ≤ .02 mg/L | all year | 001 |
| Chlorine, total residual | 30-day average | ≤ .864 lb/d | all year | 001 |
| Chlorine, total residual | daily maximum | ≤ 1.469 lb/d | all year | 001 |
| Chromium, total [as Cr] | 30-day average | ≤ .2 mg/L | all year | 002 |
| Chromium, total [as Cr] | daily maximum | ≤ .2 mg/L | all year | 002 |
| Zinc, total [as Zn] | 30-day average | ≤ 1 mg/L | all year | 002 |
| Zinc, total [as Zn] | daily maximum | ≤ 1 mg/L | all year | 002 |
| Chlorine, free available | 30-day average | ≤ .2 mg/L | all year | 002 |
| Chlorine, free available | daily maximum | ≤ .5 mg/L | all year | 002 |
| Chlorination duration | daily maximum | ≤ 2 hr/d | all year | 002 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 003 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 003 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 003 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 003 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 004 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 004 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 004 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 004 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 005 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 005 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 005 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 005 |
| pH | daily minimum | ≥ 6 SU | all year | 006 |
| pH | daily maximum | ≤ 9 SU | all year | 006 |
| Solids, total suspended | daily maximum | ≤ 50 mg/L | all year | 006 |
| Parameter | New limit | New or tighter | Median, last 12 months | × new limit |
|---|---|---|---|---|
| Aluminum, total [as Al], 30-day average | 0.89 mg/L | new | — | — |
| Aluminum, total [as Al], daily maximum | 2.5 mg/L | new | — | — |
| Iron, total [as Fe], 30-day average | 1 mg/L | new | — | — |
| Iron, total [as Fe], daily maximum | 1 mg/L | new | — | — |
Cited limits by parameter: Iowa's rules and the federal ones.
Same industry: the 14 Electric Services permits in Iowa.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/IA0002534 · MCP: https://passage-data.com/mcp