Passage Data · Check a report · Use it from your AI

FPL - Port Everglades

Electric Services, major discharger, Fort Lauderdale, Florida. NPDES permit FL0001538, in force until Dec 8, 2027. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 90 days after each period: outfall 001 form 1 monthly (4 values), outfall 001 form Q quarterly (6 values), outfall 002 form 1 monthly (1 value), outfall 002 form Q quarterly (8 values), outfall 012 form 1 monthly (2 values), outfall 012 form Q quarterly (10 values), and 2 more forms
Renewal application due
Jun 11, 2027 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 0 of 62 reports late

Limits in force (45)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year001
Oxygen, dissolved [DO]monthly averagereport only (mg/L)all year001
Oxygen, dissolved [DO]monthly averagereport only (mg/L)all year001
Oxygen, dissolved percent saturationmonthly averagereport only (%)all year001
Oxygen, dissolved percent saturation12-month total≤ 1 # exceedall year001
Nitrogen, total [as N]12-month totalreport only (lb/yr)all year001
Phosphorus, total [as P]12-month totalreport only (lb/yr)all year001
Oxidants, total residualmonthly average≤ .01 mg/Lall year001
Oxidants, total residualdaily maximum≤ .01 mg/Lall year001
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year001
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year001
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year001
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year001
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year001
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year002
Solids, total suspendeddaily maximum≤ 100 mg/Lall year002
Oil & Greasedaily maximum≤ 20 mg/Lall year002
Oil & Greasemonthly average≤ 15 mg/Lall year002
Nitrogen, total [as N]monthly averagereport only (mg/L)all year002
Nitrogen, total [as N]daily maximumreport only (mg/L)all year002
Phosphorus, total [as P]monthly average minimumreport only (mg/L)all year002
Phosphorus, total [as P]daily maximumreport only (mg/L)all year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
pHdaily minimum≥ 6 SUall year012
pHdaily maximum≤ 9 SUall year012
Solids, total suspendedmonthly average≤ 30 mg/Lall year012
Solids, total suspendeddaily maximum≤ 100 mg/Lall year012
Oil & Greasemonthly average≤ 15 mg/Lall year012
Oil & Greasedaily maximum≤ 20 mg/Lall year012
Nitrogen, total [as N]monthly averagereport only (mg/L)all year012
Nitrogen, total [as N]daily maximumreport only (mg/L)all year012
Phosphorus, total [as P]monthly averagereport only (mg/L)all year012
Phosphorus, total [as P]daily maximumreport only (mg/L)all year012
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year012
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year012
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year113
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year113
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year113
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year113
Temp. diff. between intake and dischargemonthly averagereport only (deg F)all year113
Temp. diff. between intake and dischargedaily maximumreport only (deg F)all year113
Chlorination durationmonthly average≤ 120 min/dall year113
Chlorination durationdaily maximum≤ 120 min/dall year113

How strict are these limits?

Cited limits by parameter: Florida's rules and the federal ones.

Same industry: the 30 Electric Services permits in Florida.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/FL0001538 · MCP: https://passage-data.com/mcp