Passage Data · Check a report · Use it from your AI

FPL Cape Canaveral Plant

Electric Services, major discharger, Cocoa, Florida. NPDES permit FL0001473, in force until Dec 8, 2027. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 90 days after each period: outfall 012 form 1 monthly (9 values), outfall 012 form Q quarterly (6 values), outfall 015 form 1 monthly (3 values), outfall 017 form 1 monthly (2 values), outfall 017 form Q quarterly (8 values), outfall 019 form 1 monthly (2 values), and 4 more forms
Renewal application due
Jun 11, 2027 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 65 reports late

Limits in force (46)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitdaily averagereport only (deg F)all year012
Temperature, water deg. fahrenheitmaximum monthly averagereport only (deg F)all year012
Oxygen, dissolved [DO]minimumreport only (mg/L)all year012
Oxygen, dissolved [DO]minimumreport only (mg/L)all year012
Oxygen, dissolved percent saturationmonthly average minimumreport only (%)all year012
Oxygen, dissolved percent saturation12-month total≤ 1 # exceedall year012
Nitrogen, total [as N]annual total≤ 2555 lb/yrall year012
Nitrogen, total [as N]quarterly totalreport only (lb/qtr)all year012
Phosphorus, total [as P]quarterly totalreport only (lb/qtr)all year012
Phosphorus, total [as P]annual total≤ 146 lb/yrall year012
Oxidants, total residualdaily maximum≤ .01 mg/Lall year012
Flow, in conduit or thru treatment plantinstantaneous maximumreport only (MGD)all year012
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year012
Chlorine dioxidedaily maximumreport only (mg/L)all year012
Temp. diff. between intake and dischargemaximum monthly average≤ 14.2 deg FMay–Sep012
Temp. diff. between intake and dischargedaily averagereport only (deg F)May–Sep012
Temp. diff. between intake and dischargedaily averagereport only (deg F)Jan, Feb, Mar, Apr, Oct, Nov, Dec012
Temp. diff. between intake and dischargemaximum monthly averagereport only (deg F)Jan, Feb, Mar, Apr, Oct, Nov, Dec012
Chlorination durationinstantaneous maximum≤ 120 min/dall year012
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year012
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year012
IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 100 %all year012
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year012
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year012
IC25 Static Renewal 7 Day Chronic Menidia menidiaminimum≥ 100 %all year012
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year015
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year015
Chlorination durationinstantaneous maximum≤ 1440 min/dall year015
pHinstantaneous minimum≥ 6 SUall year017
pHinstantaneous maximum≤ 9 SUall year017
Solids, total suspendedmonthly average≤ 30 mg/Lall year017
Solids, total suspendeddaily maximum≤ 100 mg/Lall year017
Oil & Greasemonthly average≤ 15 mg/Lall year017
Oil & Greasedaily maximum≤ 20 mg/Lall year017
Nitrogen, total [as N]maximumreport only (mg/L)all year017
Phosphorus, total [as P]maximumreport only (mg/L)all year017
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year017
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year017
Solids, total suspendedmonthly average≤ 30 mg/Lall year019
Solids, total suspendeddaily maximum≤ 100 mg/Lall year019
Oil & Greasemonthly average≤ 15 mg/Lall year019
Oil & Greasedaily maximum≤ 20 mg/Lall year019
Nitrogen, total [as N]maximumreport only (mg/L)all year019
Phosphorus, total [as P]maximumreport only (mg/L)all year019
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year019
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year019

How strict are these limits?

Cited limits by parameter: Florida's rules and the federal ones.

Same industry: the 30 Electric Services permits in Florida.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/FL0001473 · MCP: https://passage-data.com/mcp