Orlando Utilities Commission

NPDES permit FL0000680 · Major NON-POTW · effective, expires 2028-04-19 · EPA's file as of 2026-09-19

Check this month's numbers before you file

EPA's record, 2025-09-01 to 2026-08-31

0values over a limit
0required values missing, on 0 form(s)
0of 27 forms filed late

Last period with anything received: 2026-07-31.

Reporting

Reports are due about 28 days after each monitoring period ends (the most common figure among FL permits in EPA's filings — check your permit).

Limits in force (48)

OutfallParameterStatisticLimitMonths
001Temperature, water deg. fahrenheitDAILY MX report only all year
001Temperature, water deg. fahrenheitDAILY MX report only all year
001Plant capacity fact. percent of capacityMO TOTAL report only all year
001Oxygen, dissolved [DO]DAILY MN report only all year
001Oxygen, dissolved [DO]DAILY MN report only all year
001Oxygen, dissolved percent saturationMO AV MN report only all year
001Oxygen, dissolved percent saturationANNL TOT <= 1 # exceed all year
001pHDAILY MN >= 6.5 SU all year
001pHDAILY MX <= 8.5 SU all year
001Nickel, total recoverableMO AVG <= 8.3 ug/L all year
001Nickel, total recoverableMO AVG report only all year
001Nickel, total recoverableDAILY MX <= 8.3 ug/L all year
001Nickel, total recoverableDAILY MX report only all year
001Nickel, total recoverableDAILY MX report only all year
001Nickel, total recoverableMO AVG report only all year
001Copper, total recoverableMO AVG report only all year
001Copper, total recoverableMO AVG <= 3.7 ug/L all year
001Copper, total recoverableDAILY MX report only all year
001Copper, total recoverableDAILY MX <= 3.7 ug/L all year
001Copper, total recoverableMO AVG report only all year
001Copper, total recoverableDAILY MX report only all year
001Flow, in conduit or thru treatment plantMO AVG report only all year
001Flow, in conduit or thru treatment plantDAILY MX <= 820 MGD all year
001Temp. diff. between intake and dischargeWKLY AVG <= 19 deg F Jun, Jul, Aug, Sep
001Temp. diff. between intake and dischargeDAILY MX report only Jan, Feb, Mar, Apr, May, Oct, Nov, Dec
001LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)MINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)MINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)MINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)MINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute MenidiaMINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute MenidiaMINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute MenidiaMINIMUM >= 100 % all year
001LC50 Static Renewal 96Hr Acute MenidiaMINIMUM >= 100 % all year
016Solids, total suspendedMO AVG <= 30 mg/L all year
016Solids, total suspendedDAILY MX <= 100 mg/L all year
016Oil & GreaseMO AVG <= 15 mg/L all year
016Oil & GreaseDAILY MX <= 20 mg/L all year
016Nitrogen, total [as N]MAXIMUM report only all year
016Nitrogen, total [as N]ANNL TOT <= 40 lb/yr all year
016Nitrogen, total [as N]MO TOTAL report only all year
016Phosphorus, total [as P]ANNL TOT <= 20 lb/yr all year
016Phosphorus, total [as P]MO TOTAL report only all year
016Nickel, total recoverableDAILY MX report only all year
016Nickel, total recoverableMO AVG report only all year
016Copper, total recoverableDAILY MX report only all year
016Copper, total recoverableMO AVG report only all year
016Flow, in conduit or thru treatment plantMX MO AV <= .297 MGD all year
016Flow, in conduit or thru treatment plantMO AVG report only all year

Built from EPA's ECHO bulk files. EPA's file, not the permit document, is the source: read your permit. Check a report before you file it · All states