Passage Data · Check a report · Use it from your AI

Bridgeport Energy LLC

Electric Services, major discharger, Bridgeport, Connecticut. NPDES permit CT0030180 expired Dec 29, 2010; its limits still apply. Last 12 months: no values over a limit, 1 of 33 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 31 days after each period: outfall 100 form 1 monthly (22 values), outfall 100 form M monthly (6 values), outfall 102 form 1 monthly (20 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
4 values over a limit, 70 required values missing, 8 of 36 reports late

Limits in force (52)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitinstantaneous maximum≤ 106 deg Fall year100
Temperature, water deg. fahrenheitinstantaneous maximum≤ 106 deg Fall year100
Temperature, water deg. fahrenheitinstantaneous maximumreport only (deg F)all year100
Temperature, water deg. fahrenheitinstantaneous maximumreport only (deg F)all year100
pHinstantaneous minimum≥ 6 SUall year100
pHinstantaneous minimum≥ 6 SUall year100
pHinstantaneous maximum≤ 9 SUall year100
pHinstantaneous maximum≤ 9 SUall year100
Copper, total [as Cu]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Copper, total [as Cu]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Copper, total [as Cu]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Copper, total [as Cu]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Zinc, total [as Zn]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Zinc, total [as Zn]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Zinc, total [as Zn]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Zinc, total [as Zn]instantaneous maximumreport only (ug/L)Mar, Jun, Sep, Dec100
Oxidants, total residualinstantaneous maximum≤ 200 ug/Lall year100
Oxidants, total residualinstantaneous maximum≤ 200 ug/Lall year100
Flow, maximum during 24 hr perioddaily maximum≤ 168 MGDall year100
Flow, maximum during 24 hr perioddaily maximum≤ 168 MGDall year100
Temp. diff. between intake and dischargeinstantaneous maximum≤ 32 deg Fall year100
Temp. diff. between intake and dischargeinstantaneous maximum≤ 32 deg Fall year100
Flowdaily maximum≤ 168 MGDall year100
Flowdaily maximum≤ 168 MGDall year100
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)Mar, Sep100
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)Mar, Sep100
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)Jan, Feb, Apr, May, Jun, Jul, Aug, Oct, Nov, Dec100
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)Jan, Feb, Apr, May, Jun, Jul, Aug, Oct, Nov, Dec100
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)Mar, Sep100
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)Mar, Sep100
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)Jan, Feb, Apr, May, Jun, Jul, Aug, Oct, Nov, Dec100
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)Jan, Feb, Apr, May, Jun, Jul, Aug, Oct, Nov, Dec100
pHinstantaneous minimum≥ 6 SUall year102
pHinstantaneous minimum≥ 6 SUall year102
pHinstantaneous maximum≤ 9 SUall year102
pHinstantaneous maximum≤ 9 SUall year102
Iron, total [as Fe]instantaneous maximumreport only (mg/L)all year102
Iron, total [as Fe]instantaneous maximumreport only (mg/L)all year102
Manganese, total [as Mn]instantaneous maximumreport only (mg/L)all year102
Manganese, total [as Mn]instantaneous maximumreport only (mg/L)all year102
Zinc, total [as Zn]instantaneous maximumreport only (mg/L)all year102
Zinc, total [as Zn]instantaneous maximumreport only (mg/L)all year102
Aluminum, total [as Al]instantaneous maximumreport only (mg/L)all year102
Aluminum, total [as Al]instantaneous maximumreport only (mg/L)all year102
Oxidants, total residualinstantaneous maximumreport only (mg/L)all year102
Oxidants, total residualinstantaneous maximumreport only (mg/L)all year102
Flow, maximum during 24 hr perioddaily maximum≤ 75000 gal/dall year102
Flow, maximum during 24 hr perioddaily maximum≤ 75000 gal/dall year102
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)all year102
Pass/Fail Static 4 Day Chronic Mysidopsis Bahiaaveragereport only (pass=0;fail=1)all year102
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)all year102
Pass/Fail Static 4 Day Chronic Cyprinodon Variegaaveragereport only (pass=0;fail=1)all year102

How strict are these limits?

Cited limits by parameter: Connecticut's rules and the federal ones.

Same industry: the 12 Electric Services permits in Connecticut.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/CT0030180 · MCP: https://passage-data.com/mcp