NPDES permit CO0020184 · Minor NON-POTW · administratively continued, expires 2015-05-31 · EPA's file as of 2026-09-19
Check this month's numbers before you fileThis permit expired on 2015-05-31 and is administratively continued: its last limits keep applying until a new permit is issued, and EPA still expects the reports.
Last period with anything received: 2026-07-31.
Reports are due about 28 days after each monitoring period ends (read off this permit's own late-day counts in EPA's filings).
| Outfall | Parameter | Statistic | Limit | Months |
|---|---|---|---|---|
| 001 | Temperature, water deg. centigrade | MX WK AV | report only | all year |
| 001 | Temperature, water deg. centigrade | DAILY MX | report only | all year |
| 001 | BOD, 5-day, 20 deg. C | 30DA AVG | <= 30 mg/L | all year |
| 001 | BOD, 5-day, 20 deg. C | MX 7D AV | <= 45 mg/L | all year |
| 001 | pH | MINIMUM | >= 6.5 SU | all year |
| 001 | pH | MAXIMUM | <= 9 SU | all year |
| 001 | Solids, total suspended | 30DA AVG | <= 30 mg/L | all year |
| 001 | Solids, total suspended | MX 7D AV | <= 45 mg/L | all year |
| 001 | Nitrogen, ammonia total [as N] | 30DA AVG | <= 14.1 mg/L | all year |
| 001 | Nitrogen, ammonia total [as N] | DAILY MX | report only | all year |
| 001 | Oil and grease | INST MAX | <= 10 mg/L | all year |
| 001 | E. coli, thermotol, MF, MTEC | 30DA AVG | <= 126 #/100mL | all year |
| 001 | E. coli, thermotol, MF, MTEC | MX 7D AV | <= 252 #/100mL | all year |
| 001 | Flow, in conduit or thru treatment plant | 30DA AVG | <= .11 MGD | all year |
| 001 | Flow, in conduit or thru treatment plant | DAILY MX | report only | all year |
| 001 | Chlorine, total residual | 30DA AVG | <= .053 mg/L | all year |
| 001 | Chlorine, total residual | INST MAX | <= .19 mg/L | all year |
| 001 | BOD, 5-day, percent removal | MINIMUM | >= 85 % | all year |
| 001 | Solids, suspended percent removal | MINIMUM | >= 85 % | all year |
| 001 | Oil and grease visual | INST MAX | report only | all year |
| 300 | BOD, 5-day, 20 deg. C | 30DA AVG | report only | all year |
| 300 | BOD, 5-day, 20 deg. C | DAILY MX | report only | all year |
| 300 | BOD, 5-day, 20 deg. C | 30DA AVG | report only | all year |
| 300 | BOD, 5-day, 20 deg. C | DAILY MX | report only | all year |
| 300 | Solids, total suspended | 30DA AVG | report only | all year |
| 300 | Solids, total suspended | DAILY MX | report only | all year |
| 300 | Flow, in conduit or thru treatment plant | 30DA AVG | report only | all year |
| 300 | Flow, in conduit or thru treatment plant | DAILY MX | report only | all year |