Passage Data · Cited limits by place · Use it from your AI

Free available chlorine in Texas (US-TX): 40 CFR Part 423 — Steam electric power generating point source category

16 rows for free available chlorine in this instrument. Every instrument for free available chlorine in Texas

United States (US): 16 rows

Effluent: 16 rows

40 CFR Part 423 — Steam electric power generating point source category · eCFR as of 2026-10-05 · 16 limits
Every row: discharge to surface water
ValueApplies whenCite
0.5 mg/Lexisting sources (BPT)
(6) The quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentation listed in the following table:
40 CFR 423.12 (BPT)
Free available chlorine 0.5 0.2
0.2 mg/Las aboveas above
0.5 mg/Lexisting sources (BPT)
(7) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown sources times the concentration listed in the following table:
as above
0.2 mg/Las aboveas above
0.5 mg/Lexisting sources (BAT)
(c)(1) For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
40 CFR 423.13 (BAT)
Free available chlorine 0.5 0.2
0.2 mg/Las aboveas above
0.5 mg/Lexisting sources (BAT)
(d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
0.2 mg/Las aboveas above
0.5 mg/Lnew sources (NSPS)
(9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
40 CFR 423.15 (NSPS)
Free available chlorine 0.5 0.2
0.2 mg/Las aboveas above
0.5 mg/Lnew sources (NSPS)
(10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
0.2 mg/Las aboveas above
0.5 mg/Lnew sources (NSPS)
(9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
as above
0.2 mg/Las aboveas above
0.5 mg/Lnew sources (NSPS)
(10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
0.2 mg/Las aboveas above

Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.