Passage Data · Cited limits by place · Use it from your AI
9 cited rows from 3 instruments, North Dakota's own first. Not covered: a permit's own limits, or rules outside the 69 instruments we hold for North Dakota (US-ND) and United States. Everything held for North Dakota
North Dakota: surface water 1 · United States: drinking water 2, effluent 6
| Parameter | Value | Applies when | Cite |
|---|---|---|---|
| Nitrate + nitrite as N | 10 mg/L | receiving water: freshwater waters used as a municipal or domestic drinking water supply | N.D. Admin. Code 33.1-16-02.1-09 Table 1 · p. 13However, in no case shall the concentration for nitrate plus nitrite N exceed 10 mg/l for any waters used as a municipal or domestic drinking water supply. |
Free check: send your permit or lab results and we check each number against the limits that apply here, each verdict cited to its page, by email within 5 business days. Or send a link to a rule we do not hold: we read it and cite it by page.
| Parameter | Value | Kind | Applies when | Cite |
|---|---|---|---|---|
| Total Nitrate and Nitrite | 10 (as Nitrogen) mg/l | limit | 40 CFR 141.2: Maximum contaminant level means the maximum permissible level of a contaminant in water which is delivered to any user of a public water system. | 141.62 |
| Total Nitrate + Nitrite | 10 (as Nitrogen) mg/l | guideline | 40 CFR 141.2: Maximum contaminant level goals are nonenforceable health goals. | 141.51 |
| Parameter | Value | Statistic | Applies when | Cite |
|---|---|---|---|---|
| Nitrate/Nitrite | 2.0 mg/L | daily maximum | discharge to surface water existing sources (BAT) (3) Voluntary incentives plan. (i) For dischargers who voluntarily choose to meet the effluent limitations for FGD wastewater in this paragraph (g)(3)(i), the quantity of pollutants in FGD wastewater shall not exceed the quantity determined by multiplying the flow of FGD wastewater times the concentration listed in table 7 to this paragraph (g)(3)(i). Dischargers who choose to meet the effluent… table: Table 7 to Paragraph ( g )(3)( i ) | 40 CFR 423.13 (BAT)Nitrate/Nitrite (mg/L) 2.0 1.2 |
| Nitrate/Nitrite | 1.2 mg/L | monthly average | as above | as above |
| Nitrate/nitrite as N | 4 mg/L | daily maximum | discharge to surface water existing sources (BAT) (g) FGD wastewater —(1) 2020 BAT. (i) Except for those discharges to which paragraph (g)(2) or (3) of this section applies, the quantity of pollutants in FGD wastewater shall not exceed the quantity determined by multiplying the flow of FGD wastewater times the concentration listed in table 5 to this paragraph (g)(1)(i). Dischargers must meet the effluent limitations for FGD wastewater in this … table: Table 5 to Paragraph ( g )(1)( i ) | 40 CFR 423.13 (BAT)Nitrate/nitrite as N (mg/L) 4 3 |
| Nitrate/nitrite as N | 3 mg/L | monthly average | as above | as above |
| Nitrate/nitrite as N | 4 mg/L | daily maximum | discharge to a sewer (pretreatment) existing sources (PSES) (e) FGD wastewater —(1) 2020 PSES. Except as provided for in paragraph (e)(2) of this section, for any electric generating unit with a total nameplate generating capacity of more than 50 megawatts, that is not an oil-fired unit, and that the owner has not certified that it will cease coal combustion pursuant to § 423.19(g), the quantity of pollutants in FGD wastewater shall not exceed the quant… table: Table 3 to Paragraph (e)(1) | 40 CFR 423.16 (PSES)Nitrate/nitrite as N (mg/L) 4 3 |
| Nitrate/nitrite as N | 3 mg/L | monthly average | as above | as above |
69 instruments we hold for North Dakota (US-ND) and United States, for 11 names matching “nitrate nitrite” (each in the JSON). 3 have a row, in the tables above; 66 have none.
The address: https://passage-data.com/mcp
In a chat app
In a coding tool
claude mcp add --transport http passage-data https://passage-data.com/mcp codex mcp add passage-data --url https://passage-data.com/mcp gemini mcp add --transport http passage-data https://passage-data.com/mcp Then ask it, for example: “What are the nitrate/nitrite limits in North Dakota? Cite each one.”
Programs: this page as JSON at /api/v1/limits?parameter=nitrate%20nitrite&place=US-ND; MCP at https://passage-data.com/mcp (tool find_limits). Every tool · llms.txt · OpenAPI
Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.