Passage Data · Cited limits by place · Use it from your AI

BOD in Michigan (US-MI): 40 CFR Part 419 — Petroleum refining point source category

56 rows for bod in this instrument. Every instrument for bod in Michigan

United States (US): 56 rows

Effluent: 56 rows

40 CFR Part 419 — Petroleum refining point source category · eCFR as of 2026-10-05 · 56 limits
Every row: discharge to surface water
ParameterValueStatisticApplies whenCite
BOD50.6 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart D—Lube Subcategory
existing sources (BPT)
40 CFR 419.42 (BPT)
BOD 5 50.6 25.8
BOD25.8 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD522.7 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BPT)
40 CFR 419.12 (BPT)
BOD 5 22.7 12.0
BOD512.0 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD50.048 kilograms per cubic meter of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BPT)
(c) The following allocations constitute the quantity and quality of pollutants or pollutant properties controlled by this paragraph and attributable to ballast, which may be discharged after the application of best practicable control technology currently available, by a point source subject to this subpart, in addition to the discharge allowed by paragraph (b) of this section. The allocation …
40 CFR 419.12 (BPT)
BOD 5 0.048 0.026
BOD50.026 kilograms per cubic meter of flowmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BPT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease or 110 mg/l TOC is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by th…
40 CFR 419.12 (BPT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD522.7 Kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BCT)
(a) Any existing point source subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT).
40 CFR 419.14 (BCT)
BOD 5 22.7 12.0
BOD512.0 Kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD50.048 kilograms per m³ of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BCT)
(c) The following allocations constitute the quantity and quality of pollutants or pollutant properties controlled by this paragraph and attributable to ballast, which may be discharged after the application of best conventional pollutant control technology by a point source subject to this subpart, in addition to the discharge allowed by paragraph (b) of this section. The allocation allowed fo…
40 CFR 419.14 (BCT)
BOD 5 0.048 0.026
BOD50.026 kilograms per m³ of flowmonthly averageas aboveas above
BOD548. kilograms per 1,000 (m³ of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
existing sources (BCT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer …
40 CFR 419.14 (BCT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 (m³ of flowmonthly averageas aboveas above
BOD511.8 kilograms per cubic meter of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
new sources (NSPS)
(a) Any new source subject to this subpart must achieve the following new source performance standards (NSPS):
40 CFR 419.16 (NSPS)
BOD 5 11.8 6.3
BOD56.3 kilograms per cubic meter of flowmonthly averageas aboveas above
BOD50.048 kilograms per cubic meter of flowdaily maximumthe discharge is of the Subpart A—Topping Subcategory
new sources (NSPS)
(c) The following allocations constitute the quantity and quality of pollutants or pollutant properties controlled by this paragraph and attributable to ballast, which may be discharged after the application of best practicable control technology currently available, by a point source subject to this subpart, in addition to the discharge allowed by paragraph (b) of this section. The allocation …
40 CFR 419.16 (NSPS)
BOD 5 0.048 0.026
BOD50.026 kilograms per cubic meter of flowmonthly averageas aboveas above
BOD528.2 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart B—Cracking Subcategory
existing sources (BPT)
40 CFR 419.22 (BPT)
BOD 5 28.2 15.6
BOD515.6 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart B—Cracking Subcategory
existing sources (BPT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease or 110 mg/l TOC is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by th…
40 CFR 419.22 (BPT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD528.2 kilograms per 1,000 (m³ of feedstockdaily maximumthe discharge is of the Subpart B—Cracking Subcategory
existing sources (BCT)
(a) Any existing point source subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT):
40 CFR 419.24 (BCT)
BOD 5 28.2 15.6
BOD515.6 kilograms per 1,000 (m³ of feedstockmonthly averageas aboveas above
BOD548 kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart B—Cracking Subcategory
existing sources (BCT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer …
40 CFR 419.24 (BCT)
BOD 5 48 26
BOD526 kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD516.3 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart B—Cracking Subcategory
new sources (NSPS)
(a) Any new source subject to this subpart must achieve the following new source performance standards (NSPS):
40 CFR 419.26 (NSPS)
BOD 5 16.3 8.7
BOD58.7 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD534.6 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart C—Petrochemical Subcategory
existing sources (BPT)
40 CFR 419.32 (BPT)
BOD 5 34.6 18.4
BOD518.4 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart C—Petrochemical Subcategory
existing sources (BPT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease or 110 mg/l TOC is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by th…
40 CFR 419.32 (BPT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD534.6 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart C—Petrochemical Subcategory
existing sources (BCT)
(a) Any existing point source subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT):
40 CFR 419.34 (BCT)
BOD 5 34.6 18.4
BOD518.4 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart C—Petrochemical Subcategory
existing sources (BCT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer …
40 CFR 419.34 (BCT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD521.8 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart C—Petrochemical Subcategory
new sources (NSPS)
(a) Any new source subject to this subpart must achieve the following new source performance standards (NSPS):
40 CFR 419.36 (NSPS)
BOD 5 21.8 11.6
BOD511.6 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart D—Lube Subcategory
existing sources (BPT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease or 110 mg/l TOC is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by th…
40 CFR 419.42 (BPT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD550.6 Metric units (kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart D—Lube Subcategory
existing sources (BCT)
(a) Any existing point source subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT):
40 CFR 419.44 (BCT)
BOD 5 50.6 25.8
BOD525.8 Metric units (kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. Metric unit (kilograms per 1,000 m³ of flow)daily maximumthe discharge is of the Subpart D—Lube Subcategory
existing sources (BCT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer …
40 CFR 419.44 (BCT)
BOD 5 48. 26.
BOD526. Metric unit (kilograms per 1,000 m³ of flow)monthly averageas aboveas above
BOD534.6 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart D—Lube Subcategory
new sources (NSPS)
(a) Any new source subject to this subpart must achieve the following new source performance standards (NSPS):
40 CFR 419.46 (NSPS)
BOD 5 34.6 18.4
BOD518.4 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD554.4 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart E—Integrated Subcategory
existing sources (BPT)
40 CFR 419.52 (BPT)
BOD 5 54.4 28.9
BOD528.9 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of flowdaily maximumthe discharge is of the Subpart E—Integrated Subcategory
existing sources (BPT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease or 110 mg/l TOC is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by th…
40 CFR 419.52 (BPT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of flowmonthly averageas aboveas above
BOD554.4 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart E—Integrated Subcategory
existing sources (BCT)
(a) Any existing point subject to this subpart must achieve the following effluent limitations representing the degree of effluent reduction attainable by the application of the best conventional pollutant control technology (BCT):
40 CFR 419.54 (BCT)
BOD 5 54.4 28.9
BOD528.9 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD548. kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart E—Integrated Subcategory
existing sources (BCT)
(2) If contaminated runoff is commingled or treated with process wastewater, or if wastewater consisting solely of contaminated runoff which exceeds 15 mg/l oil and grease is not commingled or treated with any other type of wastewater, the quantity of pollutants discharged shall not exceed the quantity determined by multiplying the flow of contaminated runoff as determined by the permit writer …
40 CFR 419.54 (BCT)
BOD 5 48. 26.
BOD526. kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above
BOD541.6 kilograms per 1,000 m³ of feedstockdaily maximumthe discharge is of the Subpart E—Integrated Subcategory
new sources (NSPS)
(a) Any new source subject to this subpart must achieve the following new source performance standards (NSPS):
40 CFR 419.56 (NSPS)
BOD 5 41.6 22.1
BOD522.1 kilograms per 1,000 m³ of feedstockmonthly averageas aboveas above

Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.