Passage Data · Cited limits by place · Use it from your AI

Chlorine in Illinois (US-IL): 40 CFR Part 423 — Steam electric power generating point source category

19 rows for chlorine in this instrument. Every instrument for chlorine in Illinois

United States (US): 19 rows

Effluent: 19 rows

40 CFR Part 423 — Steam electric power generating point source category · eCFR as of 2026-10-05 · 19 limits
Every row: discharge to surface water
ParameterValueApplies whenCite
Total residual chlorine0.20 mg/Lexisting sources (BAT)
(b)(1) For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table:
40 CFR 423.13 (BAT)
Total residual chlorine 0.20
Total residual chlorine0.20 mg/Lnew sources (NSPS)
(8)(i) Once through cooling water. For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table:
40 CFR 423.15 (NSPS)
Total residual chlorine 0.20
Total residual chlorine0.20 mg/Las aboveas above
Free available chlorine0.5 mg/Lexisting sources (BPT)
(6) The quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentation listed in the following table:
40 CFR 423.12 (BPT)
Free available chlorine 0.5 0.2
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lexisting sources (BPT)
(7) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown sources times the concentration listed in the following table:
as above
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lexisting sources (BAT)
(c)(1) For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
40 CFR 423.13 (BAT)
Free available chlorine 0.5 0.2
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lexisting sources (BAT)
(d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lnew sources (NSPS)
(9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
40 CFR 423.15 (NSPS)
Free available chlorine 0.5 0.2
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lnew sources (NSPS)
(10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lnew sources (NSPS)
(9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table:
as above
Free available chlorine0.2 mg/Las aboveas above
Free available chlorine0.5 mg/Lnew sources (NSPS)
(10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
as above
Free available chlorine0.2 mg/Las aboveas above

Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.