Passage Data · Cited limits by place · Use it from your AI

Zinc in Iowa (US-IA): 40 CFR Part 423 — Steam electric power generating point source category

9 rows for zinc in this instrument. Every instrument for zinc in Iowa

United States (US): 9 rows

Effluent: 9 rows

40 CFR Part 423 — Steam electric power generating point source category · eCFR as of 2026-10-05 · 9 limits
ParameterValueStatisticApplies whenCite
Zinc, total1.0 mg/Ldaily maximumdischarge to surface water
existing sources (BAT)
(d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
40 CFR 423.13 (BAT)
Zinc, total 1.0 1.0
Zinc, total1.0 mg/Lmonthly averageas aboveas above
zinc, total1.0 mg/Ldaily maximumdischarge to surface water
new sources (NSPS)
(10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below:
40 CFR 423.15 (NSPS)
zinc, total 1.0 1.0
zinc, total1.0 mg/Lmonthly averageas aboveas above
zinc, total1.0 mg/Ldaily maximumas aboveas above
zinc, total1.0 mg/Lmonthly averageas aboveas above
Zinc, total1.0 mg/L—discharge to a sewer (pretreatment)
existing sources (PSES)
(d)(1) The pollutants discharged in cooling tower blowdown shall not exceed the concentration listed in the following table:
40 CFR 423.16 (PSES)
Zinc, total 1.0
zinc, total1.0 mg/L—discharge to a sewer (pretreatment)
new sources (PSNS)
(4)(i) Cooling tower blowdown. The pollutants discharged in cooling tower blowdown shall not exceed the concentration listed in the following table:
40 CFR 423.17 (PSNS)
zinc, total 1.0
zinc, total1.0 mg/L—as aboveas above

Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.