Passage Data · Cited limits by place · Use it from your AI
19 rows for chlorine in this instrument. Every instrument for chlorine in District of Columbia
| Parameter | Value | Applies when | Cite |
|---|---|---|---|
| Total residual chlorine | 0.20 mg/L | existing sources (BAT) (b)(1) For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table: | 40 CFR 423.13 (BAT)Total residual chlorine 0.20 |
| Total residual chlorine | 0.20 mg/L | new sources (NSPS) (8)(i) Once through cooling water. For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table: | 40 CFR 423.15 (NSPS)Total residual chlorine 0.20 |
| Total residual chlorine | 0.20 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BPT) (6) The quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentation listed in the following table: | 40 CFR 423.12 (BPT)Free available chlorine 0.5 0.2 |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BPT) (7) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown sources times the concentration listed in the following table: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BAT) (c)(1) For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | 40 CFR 423.13 (BAT)Free available chlorine 0.5 0.2 |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BAT) (d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | new sources (NSPS) (9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | 40 CFR 423.15 (NSPS)Free available chlorine 0.5 0.2 |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | new sources (NSPS) (10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | new sources (NSPS) (9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | new sources (NSPS) (10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.