57 cited rows from 7 instruments, Colorado's own first. Not covered: a permit's own limits, or rules outside the 69 instruments we hold for Colorado (US-CO) and United States. Everything held for Colorado
United States: drinking water 6, surface water 4, effluent 41, soil 6
The one instrument we hold for Colorado (US-CO) has no row for chlorine. The rows below are from the place above it, which we search too.
| Parameter | Value | Kind | Applies when | Cite |
|---|---|---|---|---|
| Chlorine | 4 (as Cl 2 ) mg/L | guideline | 40 CFR 141.2: MRDLGs are nonenforceable health goals and do not reflect the benefit of the addition of the chemical for control of waterborne microbial contaminants. | 141.54, 141.65 |
| Chlorine | 4.0 (as Cl 2 ) mg/L | limit | 40 CFR 141.2: Maximum residual disinfectant level (MRDL) means a level of a disinfectant added for water treatment that may not be exceeded at the consumer's tap without an unacceptable possibility of adverse health effects. | as above |
| Chlorine dioxide | 0.8 (as ClO 2 ) mg/L | guideline | 40 CFR 141.2: MRDLGs are nonenforceable health goals and do not reflect the benefit of the addition of the chemical for control of waterborne microbial contaminants. | as above |
| Chlorine dioxide | 0.8 (as ClO 2 ) mg/L | limit | 40 CFR 141.2: Maximum residual disinfectant level (MRDL) means a level of a disinfectant added for water treatment that may not be exceeded at the consumer's tap without an unacceptable possibility of adverse health effects. | as above |
| Parameter | Value | Cite |
|---|---|---|
| Chlorine | 0.3 µg/L | source |
| Chlorine Dioxide | 0.42 µg/L | as above |
| Value | Applies when | Cite |
|---|---|---|
| 19 µg/L | receiving water: freshwater Freshwater CMC (acute): criterion maximum concentration, acute | National Recommended Aquatic Life Criteria tableChlorine 7782505 19 11 13 7.5 1986 |
| 11 µg/L | receiving water: freshwater Freshwater CCC (chronic): criterion continuous concentration, chronic | as above |
| 13 µg/L | receiving water: marine Saltwater CMC (acute): criterion maximum concentration, acute | as above |
| 7.5 µg/L | receiving water: marine Saltwater CCC (chronic): criterion continuous concentration, chronic | as above |
| Parameter | Value | Statistic | Applies when | Cite |
|---|---|---|---|---|
| Total Residual Chlorine | 0.0032 Kg/kkg (or pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart F—Chlor-alkali Subcategory (Chlorine and Sodium or Potassium Hydroxide Production) existing sources (BAT) table: Subpart F—Chlor-Alkali-Mercury Cells | 40 CFR 415.63 (BAT)Total Residual Chlorine 0.0032 0.0019 |
| Total Residual Chlorine | 0.0019 Kg/kkg (or pounds per 1,000 lb) of product | monthly average | as above | as above |
| Total Residual Chlorine | 0.013 Kg/kkg (or pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart F—Chlor-alkali Subcategory (Chlorine and Sodium or Potassium Hydroxide Production) existing sources (BAT) table: Subpart F—Chlor-Alkali-Diaphragm Cells | 40 CFR 415.63 (BAT)Total Residual Chlorine 0.013 0.0079 |
| Total Residual Chlorine | 0.0079 Kg/kkg (or pounds per 1,000 lb) of product | monthly average | as above | as above |
| Total Residual Chlorine | 0.0032 Kq/kkg (or pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart F—Chlor-alkali Subcategory (Chlorine and Sodium or Potassium Hydroxide Production) new sources (NSPS) (a) Any new source subject to this subpart and using the mercury cell process must achieve the following new source performance standards (NSPS): table: Subpart F—Chlor-Alkali-Mercury Cells | 40 CFR 415.65 (NSPS)Total Residual Chlorine 0.0032 0.0019 |
| Total Residual Chlorine | 0.0019 Kq/kkg (or pounds per 1,000 lb) of product | monthly average | as above | as above |
| Total Residual Chlorine | 0.013 Kq/kkg (or pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart F—Chlor-alkali Subcategory (Chlorine and Sodium or Potassium Hydroxide Production) new sources (NSPS) (b) Any new source subject to this subpart and using the diaphragm cell process must achieve the following new source performance standards (NSPS): table: Subpart F—Chlor-Alkali-Diaphragm Cells | 40 CFR 415.65 (NSPS)Total Residual Chlorine 0.013 0.0079 |
| Total Residual Chlorine | 0.0079 Kq/kkg (or pounds per 1,000 lb) of product | monthly average | as above | as above |
| Total Residual Chlorine | 0.086 Kg/kkg (or pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart AP—Hydrogen Cyanide Production Subcategory existing sources (BAT) table: Subpart AP—Hydrogen Cyanide | 40 CFR 415.423 (BAT)Total Residual Chlorine 0.086 0.051 |
| Total Residual Chlorine | 0.051 Kg/kkg (or pounds per 1,000 lb) of product | monthly average | as above | as above |
All 18 rows from 40 CFR Part 415 — Inorganic chemicals manufacturing point source category
| Parameter | Value | Statistic | Applies when | Cite |
|---|---|---|---|---|
| TRC | 0.000250 Pounds per thousand lb of product | daily maximum | the discharge is of the Subpart B—Sintering Subcategory existing sources (BAT) (a) Sintering operations with wet air pollution control system. The following table presents BAT limitations for sintering operations with wet air pollution control systems: table: Subpart B—Effluent Limitations (BAT) | 40 CFR 420.23 (BAT)TRC 3 0.000250 |
| TRC | 0.000250 Pounds per thousand lb of product | daily maximum | the discharge is of the Subpart B—Sintering Subcategory new sources (NSPS) (1) Sintering operations with wet air pollution control system. The following table presents NSPS for sintering operations with wet air pollution control systems: table: Subpart B—New Source Performance Standards (NSPS) | 40 CFR 420.24 (NSPS)TRC 3 0.000250 |
| TRC | 0.000146 Kg/kkg (pounds per 1,000 lb) of product | daily maximum | the discharge is of the Subpart C—Ironmaking Subcategory existing sources (BAT) (a) Iron blast furnace. table: Subpart C | 40 CFR 420.33 (BAT)TRC 1 0.000146 |
| TRC | 0.000146 Kg/kkg (pounds per 1,000 lb) of products | daily maximum | the discharge is of the Subpart C—Ironmaking Subcategory new sources (NSPS) (a) Iron blast furnace. table: Subpart C | 40 CFR 420.34 (NSPS)TRC 1 0.000146 |
| Parameter | Value | Applies when | Cite |
|---|---|---|---|
| Total residual chlorine | 0.20 mg/L | existing sources (BAT) (b)(1) For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table: | 40 CFR 423.13 (BAT)Total residual chlorine 0.20 |
| Total residual chlorine | 0.20 mg/L | new sources (NSPS) (8)(i) Once through cooling water. For any plant with a total rated electric generating capacity of 25 or more megawatts, the quantity of pollutants discharged in once through cooling water from each discharge point shall not exceed the quantity determined by multiplying the flow of once through cooling water from each discharge point times the concentration listed in the following table: | 40 CFR 423.15 (NSPS)Total residual chlorine 0.20 |
| Total residual chlorine | 0.20 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BPT) (6) The quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentation listed in the following table: | 40 CFR 423.12 (BPT)Free available chlorine 0.5 0.2 |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BPT) (7) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown sources times the concentration listed in the following table: | as above |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BAT) (c)(1) For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | 40 CFR 423.13 (BAT)Free available chlorine 0.5 0.2 |
| Free available chlorine | 0.2 mg/L | as above | as above |
| Free available chlorine | 0.5 mg/L | existing sources (BAT) (d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
All 19 rows from 40 CFR Part 423 — Steam electric power generating point source category
| Parameter | Value | Kind | Applies when | Cite |
|---|---|---|---|---|
| Chlorine | 0.18 mg/kg | guideline | Resident Soil (mg/kg) | source |
| Chlorine | 0.78 mg/kg | guideline | Industrial Soil (mg/kg) | as above |
| Chlorine | 0.00015 mg/kg | guideline | Protection of Groundwater SSLs: Risk-based SSL (mg/kg); SSL values are based on DAF=1 | as above |
| Chlorine | 2 mg/kg | reference value (not a limit) | Protection of Groundwater SSLs: MCL-based SSL (mg/kg); SSL values are based on DAF=1 | as above |
| Chlorine Dioxide | 2300 mg/kg | guideline | Resident Soil (mg/kg) | as above |
| Chlorine Dioxide | 34000 mg/kg | guideline | Industrial Soil (mg/kg) | as above |
Free check: send your permit or lab results and we check each number against the limits that apply here, each verdict cited to its page, by email within 5 business days. Or send a link to a rule we do not hold: we read it and cite it by page.
This page shows 40 of 57 rows: every instrument, each with its first 10 rows or all of them. All 57 as JSON, 200 a page.
5 NPDES permits in Colorado went over a chlorine limit in their last 12 months of reports: the list as JSON.
69 instruments we hold for Colorado (US-CO) and United States, for 26 names matching “chlorine” (each in the JSON). 7 have a row, in the tables above; 62 have none.
The address: https://passage-data.com/mcp
In a chat app
In a coding tool
claude mcp add --transport http passage-data https://passage-data.com/mcp codex mcp add passage-data --url https://passage-data.com/mcp gemini mcp add --transport http passage-data https://passage-data.com/mcp Then ask it, for example: “What are the chlorine limits in Colorado? Cite each one.”
Programs: this page as JSON at /api/v1/limits?parameter=chlorine&place=US-CO; MCP at https://passage-data.com/mcp (tool find_limits). Every tool · llms.txt · OpenAPI
Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.