Passage Data · Cited limits by place · Use it from your AI
16 rows for free available chlorine in this instrument. Every instrument for free available chlorine in Arkansas
| Value | Applies when | Cite |
|---|---|---|
| 0.5 mg/L | existing sources (BPT) (6) The quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentation listed in the following table: | 40 CFR 423.12 (BPT)Free available chlorine 0.5 0.2 |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | existing sources (BPT) (7) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown sources times the concentration listed in the following table: | as above |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | existing sources (BAT) (c)(1) For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | 40 CFR 423.13 (BAT)Free available chlorine 0.5 0.2 |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | existing sources (BAT) (d)(1) The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | new sources (NSPS) (9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | 40 CFR 423.15 (NSPS)Free available chlorine 0.5 0.2 |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | new sources (NSPS) (10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | new sources (NSPS) (9)(i) Once through cooling water. For any plant with a total rated generating capacity of less than 25 megawatts, the quantity of pollutants discharged in once through cooling water shall not exceed the quantity determined by multiplying the flow of once through cooling water sources times the concentration listed in the following table: | as above |
| 0.2 mg/L | as above | as above |
| 0.5 mg/L | new sources (NSPS) (10)(i) Cooling tower blowdown. The quantity of pollutants discharged in cooling tower blowdown shall not exceed the quantity determined by multiplying the flow of cooling tower blowdown times the concentration listed below: | as above |
| 0.2 mg/L | as above | as above |
Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.