{"permit":"PR0020486","name":"PRASA GUANICA","state":"PR","as_of":"2026-10-22","source":{"publisher":"U.S. EPA — ECHO / ICIS-NPDES national file","as_of":"2026-10-22","page":"/dmr/p/PR0020486"},"about":[{"label":"What it is","text":"Sewage treatment plant · rated a major discharger by EPA"},{"label":"Where","text":"Guanica, Puerto Rico","href":"https://www.openstreetmap.org/?mlat=17.9676&mlon=-66.910805#map=14/17.9676/-66.910805"},{"label":"Last 12 months","text":"Over a limit 37 times, last in August 2026 (Enterococci; Nitrogen, total [as N]; Cyanide, free available). 1 of 12 reports filed late"},{"label":"Permit","text":"In force until Jul 31, 2030"}],"renewal_due":null,"renewal_check":null,"sector":null,"limits_from_version":null,"record":{"last_filed":"2026-08-31","over":37,"over_by":[["Enterococci",22],["Nitrogen, total [as N]",8],["Cyanide, free available",5]],"window":["2025-10-01","2026-09-30"]},"over_limits":[],"limits":[{"outfall":"001","parameter":"Temperature, water deg. centigrade","parameter_code":"00010","statistic":"daily maximum","qualifier":"<=","value":"30","unit":"deg C","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Turbidity","parameter_code":"00070","statistic":"daily maximum","qualifier":"<=","value":"10","unit":"NTU","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Color [PT-CO units]","parameter_code":"00080","statistic":"daily maximum","qualifier":null,"value":null,"unit":"col unit (pc)","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Oxygen, dissolved [DO]","parameter_code":"00300","statistic":"instantaneous minimum","qualifier":">=","value":"5","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"232.7","unit":"kg/d","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":"<=","value":"349.1","unit":"kg/d","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"minimum","qualifier":">=","value":"7.3","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"maximum","qualifier":"<=","value":"8.5","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"232.7","unit":"kg/d","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":"<=","value":"349.1","unit":"kg/d","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, settleable","parameter_code":"00545","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mL/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Oil & Grease","parameter_code":"00556","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Nitrogen, total [as N]","parameter_code":"00600","statistic":"daily maximum","qualifier":"<=","value":"5000","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Copper, total [as Cu]","parameter_code":"01042","statistic":"daily maximum","qualifier":"<=","value":"3.73","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Copper, total [as Cu]","parameter_code":"01042","statistic":"daily maximum","qualifier":"<=","value":"34.91","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"weekly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"weekly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"daily maximum","qualifier":"<=","value":"28","unit":"MGD","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":"<=","value":"7.5","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Cyanide, free available","parameter_code":"51173","statistic":"daily maximum","qualifier":"<=","value":"1","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Sulfide-hydrogen sulfide [undissociated]","parameter_code":"51202","statistic":"daily maximum","qualifier":"<=","value":"2","unit":"ug/L","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Whole Effluent Toxicity [WET] - M. beryllina","parameter_code":"51712","statistic":"minimum","qualifier":null,"value":null,"unit":"%","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Whole Effluent Toxicity [WET] - Americamysis bahia (formerly Mysidopsis bahia)","parameter_code":"51713","statistic":"minimum","qualifier":null,"value":null,"unit":"%","report_only":true,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Enterococci","parameter_code":"61211","statistic":"geometric mean","qualifier":"<=","value":"35","unit":"#/100mL","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Enterococci","parameter_code":"61211","statistic":"90th percentile","qualifier":"<=","value":"130","unit":"#/100mL","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"BOD, 5-day, percent removal","parameter_code":"81010","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."},{"outfall":"001","parameter":"Solids, suspended percent removal","parameter_code":"81011","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"Composed of advanced tertiary treated wastewater."}],"next":[{"tool":"check_dmr","says":"Before your user files this permit's DMR: check_dmr sets each value beside the permit's limit for that period, with EPA's violation rule's verdict.","arguments":{"permit":"PR0020486"},"needs":{"period_end":"The reporting period: its month (2026-09).","values":"The period's values as your user will file them: [{outfall, parameter, statistic, value, unit}, ...]."},"post":"/api/v1/dmr/check","url":"https://passage-data.com/api/v1/dmr/check","page":"https://passage-data.com/dmr/?permit=PR0020486"},{"tool":"fill_dmr","says":"Has your user the plant's raw daily results? fill_dmr computes the period's DMR values from them, each with the rows it came from.","arguments":{"permit":"PR0020486"},"needs":{"period_end":"The reporting period: its month (2026-09).","rows":"The plant's results: [{date, parameter, value, unit, point}, ...]; or `table`, the lab's or plant's export as text."},"post":"/api/v1/dmr/fill","url":"https://passage-data.com/api/v1/dmr/fill","page":"https://passage-data.com/dmr/?permit=PR0020486"}]}