{"permit":"NY0004472","name":"HOLTEC INDIAN POINT 2, LLC AND HOLTEC INDIAN POINT 3, LLC","state":"NY","as_of":"2026-10-22","source":{"publisher":"U.S. EPA — ECHO / ICIS-NPDES national file","as_of":"2026-10-22","page":"/dmr/p/NY0004472"},"about":[{"label":"What it is","text":"Electric Services (EPA's industry listing) · rated a major discharger by EPA"},{"label":"Where","text":"Buchanan, New York","href":"https://www.openstreetmap.org/?mlat=41.269722&mlon=-73.952639#map=14/41.269722/-73.952639"},{"label":"Last 12 months","text":"No values over a limit. 50 required values not reported"},{"label":"Permit","text":"Expired Apr 30, 2022; its limits still apply until a new permit is issued, and EPA still expects the reports"}],"renewal_due":null,"renewal_check":{"offered_because":"permit_expired","application_due":"2021-11-01","price":"free while piloted","order_page":"https://passage-data.com/dmr/p/NY0004472#renewal","says":"Each limit a renewal could tighten or add, from the state's water-quality standards and the federal rules for this kind of discharge, each cited to its rule, beside EPA's 12-month record; a rule we do not hold is named, never guessed. A person orders it on the permit's page with their email; it is sent by email within 5 business days."},"sector":{"state":"NY","sic":"4911","permits":39,"list":"https://passage-data.com/api/v1/permits?state=NY&sic=4911","page":"https://passage-data.com/dmr/s/NY/4911"},"limits_from_version":null,"record":{"last_filed":"2026-08-31","over":0,"over_by":[],"window":["2025-10-01","2026-09-30"]},"over_limits":[],"limits":[{"outfall":"001","parameter":"Temperature, water deg. fahrenheit","parameter_code":"00011","statistic":"instantaneous maximum","qualifier":"<=","value":"110","unit":"deg F","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Temperature, water deg. fahrenheit","parameter_code":"00011","statistic":"daily maximum","qualifier":"<=","value":"110","unit":"deg F","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"minimum","qualifier":">=","value":"6","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"maximum","qualifier":"<=","value":"9","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Boron, total [as B]","parameter_code":"01022","statistic":"daily maximum","qualifier":"<=","value":"1","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Boron, total [as B]","parameter_code":"01022","statistic":"daily maximum","qualifier":"<=","value":"525","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Lithium, total [as Li]","parameter_code":"01132","statistic":"daily maximum","qualifier":"<=","value":".01","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Temperature, length of excursion","parameter_code":"45600","statistic":"maximum","qualifier":"<=","value":"15","unit":"d","report_only":false,"enforceable":true,"months":["APR","MAY","JUN"],"limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Temperature, length of excursion","parameter_code":"45600","statistic":"maximum","qualifier":"<=","value":"10","unit":"d","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":"<=","value":".2","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"DISCHARGE CANAL"},{"outfall":"01C","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"UNIT 2 WASTE DISPOSAL"},{"outfall":"01D","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"UNIT 3 WASTE DISPOSAL"},{"outfall":"01E","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"WATER FILTER  AND GAC BACKWASH"},{"outfall":"01G","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"BOILER BLOWDOWN"},{"outfall":"01G","parameter":"Phosphate, total, color method [as P]","parameter_code":"70505","statistic":"monthly average","qualifier":"<=","value":"16","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"BOILER BLOWDOWN"},{"outfall":"01G","parameter":"Phosphate, total, color method [as P]","parameter_code":"70505","statistic":"daily maximum","qualifier":"<=","value":"38","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"BOILER BLOWDOWN"},{"outfall":"01I","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"CONDENSER & SERVICE WATER"},{"outfall":"01J","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Oil & Grease","parameter_code":"00556","statistic":"daily maximum","qualifier":"<=","value":"15","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01J","parameter":"Oil and grease visual","parameter_code":"84066","statistic":"EPA's \"NONSP MX\"","qualifier":null,"value":null,"unit":"abst=0;prst=1","report_only":true,"enforceable":true,"months":"all","limit_set":"FLOOR DRAINS"},{"outfall":"01L","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"UNIT 3 CONDENSER POLISHER"},{"outfall":"01L","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"UNIT 3 CONDENSER POLISHER"},{"outfall":"01L","parameter":"pH","parameter_code":"00400","statistic":"minimum","qualifier":">=","value":"6","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"UNIT 3 CONDENSER POLISHER"},{"outfall":"01L","parameter":"pH","parameter_code":"00400","statistic":"maximum","qualifier":"<=","value":"9","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"UNIT 3 CONDENSER POLISHER"},{"outfall":"01L","parameter":"Fluoride, total [as F]","parameter_code":"00951","statistic":"daily maximum","qualifier":"<=","value":"5","unit":"lb/d","report_only":false,"enforceable":false,"months":"all","limit_set":"SEMI ANNUAL ACTION LEVELS"},{"outfall":"01L","parameter":"Copper, total [as Cu]","parameter_code":"01042","statistic":"daily maximum","qualifier":"<=","value":"1","unit":"mg/L","report_only":false,"enforceable":false,"months":"all","limit_set":"SEMI ANNUAL ACTION LEVELS"},{"outfall":"01L","parameter":"Iron, total [as Fe]","parameter_code":"01045","statistic":"daily maximum","qualifier":"<=","value":"4","unit":"mg/L","report_only":false,"enforceable":false,"months":"all","limit_set":"SEMI ANNUAL ACTION LEVELS"},{"outfall":"01L","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"UNIT 3 CONDENSER POLISHER"},{"outfall":"01N","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"REVERSE OSMOSIS REJECT"},{"outfall":"01N","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"REVERSE OSMOSIS REJECT"},{"outfall":"01N","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"REVERSE OSMOSIS REJECT"},{"outfall":"01N","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"REVERSE OSMOSIS REJECT"},{"outfall":"01N","parameter":"Oil & Grease","parameter_code":"00556","statistic":"daily maximum","qualifier":"<=","value":"15","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"REVERSE OSMOSIS REJECT"},{"outfall":"01P","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"EDUCTOR PIT"},{"outfall":"01P","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":"EDUCTOR PIT"},{"outfall":"01P","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"EDUCTOR PIT"},{"outfall":"01P","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"EDUCTOR PIT"},{"outfall":"01P","parameter":"Oil & Grease","parameter_code":"00556","statistic":"daily maximum","qualifier":"<=","value":"15","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"EDUCTOR PIT"},{"outfall":"SUM","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"SUM OF 01B, 01C, 01D, 01J, 01L"},{"outfall":"SUM","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SUM OF 01B, 01C, 01D, 01J, 01L"},{"outfall":"SUM","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SUM OF 01B, 01C, 01D, 01J, 01L"},{"outfall":"SUM","parameter":"Oil & Grease","parameter_code":"00556","statistic":"maximum","qualifier":"<=","value":"15","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SUM OF 01C, 01D AND 01L"},{"outfall":"SUM","parameter":"Oil & Grease","parameter_code":"00556","statistic":"daily maximum","qualifier":"<=","value":"15","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SUM OF 01C, 01D AND 01L"},{"outfall":"SUM","parameter":"Boron, total [as B]","parameter_code":"01022","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SUM OF 01C, 01D AND 01L"},{"outfall":"SUM","parameter":"Boron, total [as B]","parameter_code":"01022","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SUM OF 01C, 01D AND 01L"},{"outfall":"SUM","parameter":"Lithium, total [as Li]","parameter_code":"01132","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SUM OF 01C & 01D"},{"outfall":"SUM","parameter":"Lithium, total [as Li]","parameter_code":"01132","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SUM OF 01C & 01D"}],"next":[{"tool":"list_permits","says":"Screening this industry? list_permits lists every permit of it in this state in one call, each with its page and its get_permit address; `get` is the address to fetch.","arguments":{"state":"NY","sic":"4911"},"needs":{},"get":"https://passage-data.com/api/v1/permits?state=NY&sic=4911","url":"https://passage-data.com/api/v1/permits?state=NY&sic=4911","page":"https://passage-data.com/dmr/s/NY/4911"},{"tool":"check_dmr","says":"Before your user files this permit's DMR: check_dmr sets each value beside the permit's limit for that period, with EPA's violation rule's verdict.","arguments":{"permit":"NY0004472"},"needs":{"period_end":"The reporting period: its month (2026-09).","values":"The period's values as your user will file them: [{outfall, parameter, statistic, value, unit}, ...]."},"post":"/api/v1/dmr/check","url":"https://passage-data.com/api/v1/dmr/check","page":"https://passage-data.com/dmr/?permit=NY0004472"},{"tool":"fill_dmr","says":"Has your user the plant's raw daily results? fill_dmr computes the period's DMR values from them, each with the rows it came from.","arguments":{"permit":"NY0004472"},"needs":{"period_end":"The reporting period: its month (2026-09).","rows":"The plant's results: [{date, parameter, value, unit, point}, ...]; or `table`, the lab's or plant's export as text."},"post":"/api/v1/dmr/fill","url":"https://passage-data.com/api/v1/dmr/fill","page":"https://passage-data.com/dmr/?permit=NY0004472"}]}