{"permit":"NH0100161","name":"MERRIMACK W W T F","state":"NH","as_of":"2026-10-22","source":{"publisher":"U.S. EPA — ECHO / ICIS-NPDES national file","as_of":"2026-10-22","page":"/dmr/p/NH0100161"},"about":[{"label":"What it is","text":"Sewage treatment plant · rated a major discharger by EPA"},{"label":"Where","text":"Merrimack, New Hampshire","href":"https://www.openstreetmap.org/?mlat=42.809523&mlon=-71.475871#map=14/42.809523/-71.475871"},{"label":"Last 12 months","text":"Over a limit 3 times, last in August 2026 (pH)"},{"label":"Permit","text":"Expired May 31, 2019; its limits still apply until a new permit is issued, and EPA still expects the reports"}],"renewal_due":null,"renewal_check":{"offered_because":"permit_expired","application_due":"2018-12-02","price":"free while piloted","order_page":"https://passage-data.com/dmr/p/NH0100161#renewal","says":"Each limit a renewal could tighten or add, from the state's water-quality standards and the federal rules for this kind of discharge, each cited to its rule, beside EPA's 12-month record; a rule we do not hold is named, never guessed. A person orders it on the permit's page with their email; it is sent by email within 5 business days."},"sector":null,"limits_from_version":null,"record":{"last_filed":"2026-09-30","over":3,"over_by":[["pH",3]],"window":["2025-10-01","2026-09-30"]},"over_limits":[{"parameter":"pH","times":3,"find_limits":{"parameter":"ph","place":"US-NH","medium":"surface_water"},"get":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-NH&medium=surface_water"}],"limits":[{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"1199","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"daily maximum","qualifier":"<=","value":"2581","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"minimum","qualifier":">=","value":"6.5","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"maximum","qualifier":"<=","value":"9","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"1473","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"3255","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Nitrogen, ammonia total [as N]","parameter_code":"00610","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Phosphorus, total [as P]","parameter_code":"00665","statistic":"monthly average","qualifier":"<=","value":"164.8","unit":"lb/d","report_only":false,"enforceable":true,"months":["APR","MAY","JUN","JUL","AUG","SEP","OCT"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Hardness, total [as CaCO3]","parameter_code":"00900","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Nickel, total recoverable","parameter_code":"01074","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Zinc, total recoverable","parameter_code":"01094","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Aluminum, total recoverable","parameter_code":"01104","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Cadmium, total recoverable","parameter_code":"01113","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Lead, total recoverable","parameter_code":"01114","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Copper, total recoverable","parameter_code":"01119","statistic":"daily maximum","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"monthly average","qualifier":"<=","value":"5","unit":"MGD","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"weekly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"monthly average","qualifier":"<=","value":".85","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":"<=","value":"1","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"E. coli, colony forming units [CFU]","parameter_code":"51041","statistic":"monthly geometric mean","qualifier":"<=","value":"126","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"E. coli, colony forming units [CFU]","parameter_code":"51041","statistic":"daily maximum","qualifier":"<=","value":"406","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, process wastewater","parameter_code":"78886","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, process wastewater","parameter_code":"78886","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Flow, process wastewater","parameter_code":"78886","statistic":"weekly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"BOD, 5-day, percent removal","parameter_code":"81010","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"Solids, suspended percent removal","parameter_code":"81011","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"LC50 Static 48Hr Acute Ceriodaphnia dubia","parameter_code":"TAA3B","statistic":"daily minimum","qualifier":">=","value":"100","unit":"%","report_only":false,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"},{"outfall":"001","parameter":"LC50 Static 48Hr Acute Pimephales promelas","parameter_code":"TAA6C","statistic":"daily minimum","qualifier":">=","value":"100","unit":"%","report_only":false,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"TREATED SANITARY & INDUSTRIAL"}],"next":[{"tool":"find_limits","says":"What do the rules say about what it went over on? find_limits gives the cited state and federal limits for it, each with its rule; `get` is the address to fetch, and `over_limits` holds one for each parameter.","arguments":{"parameter":"ph","place":"US-NH","medium":"surface_water"},"needs":{},"get":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-NH&medium=surface_water","url":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-NH&medium=surface_water","page":"https://passage-data.com/limits/US-NH/ph"},{"tool":"check_dmr","says":"Before your user files this permit's DMR: check_dmr sets each value beside the permit's limit for that period, with EPA's violation rule's verdict.","arguments":{"permit":"NH0100161"},"needs":{"period_end":"The reporting period: its month (2026-09).","values":"The period's values as your user will file them: [{outfall, parameter, statistic, value, unit}, ...]."},"post":"/api/v1/dmr/check","url":"https://passage-data.com/api/v1/dmr/check","page":"https://passage-data.com/dmr/?permit=NH0100161"},{"tool":"fill_dmr","says":"Has your user the plant's raw daily results? fill_dmr computes the period's DMR values from them, each with the rows it came from.","arguments":{"permit":"NH0100161"},"needs":{"period_end":"The reporting period: its month (2026-09).","rows":"The plant's results: [{date, parameter, value, unit, point}, ...]; or `table`, the lab's or plant's export as text."},"post":"/api/v1/dmr/fill","url":"https://passage-data.com/api/v1/dmr/fill","page":"https://passage-data.com/dmr/?permit=NH0100161"}]}