{"permit":"MT0023566","name":"Eduro Health Care                                                               ","state":"MT","as_of":"2026-10-22","source":{"publisher":"U.S. EPA — ECHO / ICIS-NPDES national file","as_of":"2026-10-22","page":"/dmr/p/MT0023566"},"about":[{"label":"What it is","text":"Skilled Nursing Care Facilities (EPA's industry listing)"},{"label":"Where","text":"Clancy, Montana","href":"https://www.openstreetmap.org/?mlat=46.449444&mlon=-111.985278#map=14/46.449444/-111.985278"},{"label":"Last 12 months","text":"Over a limit 12 times, last in December 2025 (Solids, total suspended; E. coli, MTEC-MF; BOD, 5-day, 20 deg. C). 192 required values not reported. 4 of 12 reports filed late"},{"label":"Permit","text":"Expired Mar 31, 2022; its limits still apply until a new permit is issued, and EPA still expects the reports"}],"renewal_due":null,"renewal_check":{"offered_because":"permit_expired","application_due":"2021-10-02","price":"free while piloted","order_page":"https://passage-data.com/dmr/p/MT0023566#renewal","says":"Each limit a renewal could tighten or add, from the state's water-quality standards and the federal rules for this kind of discharge, each cited to its rule, beside EPA's 12-month record; a rule we do not hold is named, never guessed. A person orders it on the permit's page with their email; it is sent by email within 5 business days."},"sector":{"state":"MT","sic":"80","permits":2,"list":"https://passage-data.com/api/v1/permits?state=MT&sic=80"},"limits_from_version":null,"record":{"last_filed":"2026-05-31","over":12,"over_by":[["Solids, total suspended",8],["E. coli, MTEC-MF",2],["BOD, 5-day, 20 deg. C",2]],"window":["2025-10-01","2026-09-30"]},"over_limits":[{"parameter":"Solids, total suspended","times":8,"find_limits":{"parameter":"total suspended solids","place":"US-MT","medium":"water_discharge"},"get":"https://passage-data.com/api/v1/limits?parameter=total+suspended+solids&place=US-MT&medium=water_discharge"},{"parameter":"BOD, 5-day, 20 deg. C","times":2,"find_limits":{"parameter":"bod","place":"US-MT","medium":"water_discharge"},"get":"https://passage-data.com/api/v1/limits?parameter=bod&place=US-MT&medium=water_discharge"}],"limits":[{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"monthly average","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Flow rate","parameter_code":"00056","statistic":"daily maximum","qualifier":null,"value":null,"unit":"MGD","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"maximum weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"3.8","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"maximum weekly average","qualifier":"<=","value":"5.6","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"instantaneous minimum","qualifier":">=","value":"6","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"instantaneous maximum","qualifier":"<=","value":"9","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"30-day average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"maximum weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"30-day average","qualifier":"<=","value":"3.8","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"maximum weekly average","qualifier":"<=","value":"5.6","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Oil and grease, hexane extr method","parameter_code":"00552","statistic":"daily maximum","qualifier":"<=","value":"10","unit":"mg/L","report_only":false,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, total [as N]","parameter_code":"00600","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, total [as N]","parameter_code":"00600","statistic":"maximum weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, total [as N]","parameter_code":"00600","statistic":"30-day average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, total [as N]","parameter_code":"00600","statistic":"maximum weekly average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, ammonia total [as N]","parameter_code":"00610","statistic":"30-day average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, Kjeldahl, total [as N]","parameter_code":"00625","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrogen, Kjeldahl, total [as N]","parameter_code":"00625","statistic":"maximum weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrite + Nitrate total [as N]","parameter_code":"00630","statistic":"30-day average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Nitrite + Nitrate total [as N]","parameter_code":"00630","statistic":"weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Phosphorus, total [as P]","parameter_code":"00665","statistic":"monthly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Phosphorus, total [as P]","parameter_code":"00665","statistic":"maximum weekly average","qualifier":null,"value":null,"unit":"mg/L","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Phosphorus, total [as P]","parameter_code":"00665","statistic":"monthly average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Phosphorus, total [as P]","parameter_code":"00665","statistic":"weekly average","qualifier":null,"value":null,"unit":"lb/d","report_only":true,"enforceable":true,"months":["JUL","AUG","SEP"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Zinc, total recoverable","parameter_code":"01094","statistic":"monthly average","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"Zinc, total recoverable","parameter_code":"01094","statistic":"daily maximum","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"Lead, total recoverable","parameter_code":"01114","statistic":"monthly average","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"Lead, total recoverable","parameter_code":"01114","statistic":"daily maximum","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"Copper, total recoverable","parameter_code":"01119","statistic":"monthly average","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"Copper, total recoverable","parameter_code":"01119","statistic":"daily maximum","qualifier":null,"value":null,"unit":"ug/L","report_only":true,"enforceable":true,"months":["MAR","JUN","SEP","DEC"],"limit_set":"SEMI ANNUAL METALS TESTING"},{"outfall":"001","parameter":"E. coli, MTEC-MF","parameter_code":"31648","statistic":"monthly geometric mean","qualifier":"<=","value":"126","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":["APR","MAY","JUN","JUL","AUG","SEP","OCT"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"E. coli, MTEC-MF","parameter_code":"31648","statistic":"monthly geometric mean","qualifier":"<=","value":"630","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":["JAN","FEB","MAR","NOV","DEC"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"E. coli, MTEC-MF","parameter_code":"31648","statistic":"7-day maximum","qualifier":"<=","value":"252","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":["APR","MAY","JUN","JUL","AUG","SEP","OCT"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"E. coli, MTEC-MF","parameter_code":"31648","statistic":"7-day maximum","qualifier":"<=","value":"1260","unit":"CFU/100mL","report_only":false,"enforceable":true,"months":["JAN","FEB","MAR","NOV","DEC"],"limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":"<=","value":".5","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"BOD, 5-day, percent removal","parameter_code":"81010","statistic":"monthly minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"},{"outfall":"001","parameter":"Solids, suspended percent removal","parameter_code":"81011","statistic":"monthly minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":"SEWAGE TREATMENT PLANT"}],"next":[{"tool":"list_permits","says":"Screening this industry? list_permits lists every permit of it in this state in one call, each with its page and its get_permit address; `get` is the address to fetch.","arguments":{"state":"MT","sic":"80"},"needs":{},"get":"https://passage-data.com/api/v1/permits?state=MT&sic=80","url":"https://passage-data.com/api/v1/permits?state=MT&sic=80"},{"tool":"find_limits","says":"What do the rules say about what it went over on? find_limits gives the cited state and federal limits for it, each with its rule; `get` is the address to fetch, and `over_limits` holds one for each parameter.","arguments":{"parameter":"total suspended solids","place":"US-MT","medium":"water_discharge"},"needs":{},"get":"https://passage-data.com/api/v1/limits?parameter=total+suspended+solids&place=US-MT&medium=water_discharge","url":"https://passage-data.com/api/v1/limits?parameter=total+suspended+solids&place=US-MT&medium=water_discharge","page":"https://passage-data.com/limits/US-MT/total-suspended-solids"},{"tool":"check_dmr","says":"Before your user files this permit's DMR: check_dmr sets each value beside the permit's limit for that period, with EPA's violation rule's verdict.","arguments":{"permit":"MT0023566"},"needs":{"period_end":"The reporting period: its month (2026-09).","values":"The period's values as your user will file them: [{outfall, parameter, statistic, value, unit}, ...]."},"post":"/api/v1/dmr/check","url":"https://passage-data.com/api/v1/dmr/check","page":"https://passage-data.com/dmr/?permit=MT0023566"},{"tool":"fill_dmr","says":"Has your user the plant's raw daily results? fill_dmr computes the period's DMR values from them, each with the rows it came from.","arguments":{"permit":"MT0023566"},"needs":{"period_end":"The reporting period: its month (2026-09).","rows":"The plant's results: [{date, parameter, value, unit, point}, ...]; or `table`, the lab's or plant's export as text."},"post":"/api/v1/dmr/fill","url":"https://passage-data.com/api/v1/dmr/fill","page":"https://passage-data.com/dmr/?permit=MT0023566"}]}