{"permit":"ME0022659","name":"GOOD WILL HOME ASSOCIATION","state":"ME","as_of":"2026-10-22","source":{"publisher":"U.S. EPA — ECHO / ICIS-NPDES national file","as_of":"2026-10-22","page":"/dmr/p/ME0022659"},"about":[{"label":"What it is","text":"Elementary And Secondary Schools (EPA's industry listing)"},{"label":"Where","text":"Hinckley, Maine","href":"https://www.openstreetmap.org/?mlat=44.667056&mlon=-69.627972#map=14/44.667056/-69.627972"},{"label":"Last 12 months","text":"Over a limit 6 times, last in September 2026 (Flow, in conduit or thru treatment plant; E. coli, thermotol, MF, MTEC; pH). 1 of 12 reports filed late"},{"label":"Permit","text":"In force until Feb 28, 2029"}],"renewal_due":null,"renewal_check":null,"sector":{"state":"ME","sic":"82","permits":7,"list":"https://passage-data.com/api/v1/permits?state=ME&sic=82","page":"https://passage-data.com/dmr/s/ME/82"},"limits_from_version":null,"record":{"last_filed":"2026-09-30","over":6,"over_by":[["Flow, in conduit or thru treatment plant",3],["E. coli, thermotol, MF, MTEC",2],["pH",1]],"window":["2025-10-01","2026-09-30"]},"over_limits":[{"parameter":"pH","times":1,"find_limits":{"parameter":"ph","place":"US-ME","medium":"surface_water"},"get":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-ME&medium=surface_water"}],"limits":[{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"monthly average","qualifier":"<=","value":"5","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"daily maximum","qualifier":"<=","value":"8.3","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, 20 deg. C","parameter_code":"00310","statistic":"weekly average","qualifier":"<=","value":"7.5","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"minimum","qualifier":">=","value":"6","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"pH","parameter_code":"00400","statistic":"maximum","qualifier":"<=","value":"9","unit":"SU","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"30","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"50","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"monthly average","qualifier":"<=","value":"5","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"daily maximum","qualifier":"<=","value":"8.3","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":"<=","value":"45","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, total suspended","parameter_code":"00530","statistic":"weekly average","qualifier":"<=","value":"7.5","unit":"lb/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, settleable","parameter_code":"00545","statistic":"daily maximum","qualifier":"<=","value":".3","unit":"mL/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"E. coli, thermotol, MF, MTEC","parameter_code":"31633","statistic":"monthly geometric mean","qualifier":"<=","value":"100","unit":"#/100mL","report_only":false,"enforceable":true,"months":["APR","MAY","JUN","JUL","AUG","SEP","OCT"],"limit_set":null},{"outfall":"001","parameter":"E. coli, thermotol, MF, MTEC","parameter_code":"31633","statistic":"daily maximum","qualifier":"<=","value":"236","unit":"#/100mL","report_only":false,"enforceable":true,"months":["APR","MAY","JUN","JUL","AUG","SEP","OCT"],"limit_set":null},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"daily average","qualifier":"<=","value":"20000","unit":"gal/d","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Flow, in conduit or thru treatment plant","parameter_code":"50050","statistic":"daily maximum","qualifier":null,"value":null,"unit":"gal/d","report_only":true,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Chlorine, total residual","parameter_code":"50060","statistic":"daily maximum","qualifier":"<=","value":"1","unit":"mg/L","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"BOD, 5-day, percent removal","parameter_code":"81010","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":null},{"outfall":"001","parameter":"Solids, suspended percent removal","parameter_code":"81011","statistic":"monthly average minimum","qualifier":">=","value":"85","unit":"%","report_only":false,"enforceable":true,"months":"all","limit_set":null}],"next":[{"tool":"list_permits","says":"Screening this industry? list_permits lists every permit of it in this state in one call, each with its page and its get_permit address; `get` is the address to fetch.","arguments":{"state":"ME","sic":"82"},"needs":{},"get":"https://passage-data.com/api/v1/permits?state=ME&sic=82","url":"https://passage-data.com/api/v1/permits?state=ME&sic=82","page":"https://passage-data.com/dmr/s/ME/82"},{"tool":"find_limits","says":"What do the rules say about what it went over on? find_limits gives the cited state and federal limits for it, each with its rule; `get` is the address to fetch, and `over_limits` holds one for each parameter.","arguments":{"parameter":"ph","place":"US-ME","medium":"surface_water"},"needs":{},"get":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-ME&medium=surface_water","url":"https://passage-data.com/api/v1/limits?parameter=ph&place=US-ME&medium=surface_water","page":"https://passage-data.com/limits/US-ME/ph"},{"tool":"check_dmr","says":"Before your user files this permit's DMR: check_dmr sets each value beside the permit's limit for that period, with EPA's violation rule's verdict.","arguments":{"permit":"ME0022659"},"needs":{"period_end":"The reporting period: its month (2026-09).","values":"The period's values as your user will file them: [{outfall, parameter, statistic, value, unit}, ...]."},"post":"/api/v1/dmr/check","url":"https://passage-data.com/api/v1/dmr/check","page":"https://passage-data.com/dmr/?permit=ME0022659"},{"tool":"fill_dmr","says":"Has your user the plant's raw daily results? fill_dmr computes the period's DMR values from them, each with the rows it came from.","arguments":{"permit":"ME0022659"},"needs":{"period_end":"The reporting period: its month (2026-09).","rows":"The plant's results: [{date, parameter, value, unit, point}, ...]; or `table`, the lab's or plant's export as text."},"post":"/api/v1/dmr/fill","url":"https://passage-data.com/api/v1/dmr/fill","page":"https://passage-data.com/dmr/?permit=ME0022659"}]}